The cooling operation or heating operation does not operate. (LED display: Both LED1 and LED2 lighting)

C Check of R.V. coil

When heating operation does not work.

1.Disconnect the lead wire leading to the compressor.

2.3 minutes after turning on the power supply, start EMERGENCY OPERATION in HEAT mode.

Is there voltage of 230V AC between pin1 and

No

pin 2 at connector CN912? W

 

Yes

 

Turn off power supply of indoor and outdoor unit.

1.Turn off power supply of indoor and outdoor unit, and disconnect the connector CN781 in the outdoor electronic control P.C. board.

2.3 minutes after turning on the power supply, start EMERGENCY OPERATION in HEAT mode.

Disconnect the connector CN912 in noise filter P. C. board. Is there normal resistance to R.V. coil?

Yes

Replace the 4-way valve.

No

Replace the R.V. coil.

Is there voltage 12V DC

No

between the connector CN781 pin 5 (+) and pin 3 (-)?

Yes

Replace the noise filter P.C. board.

Replace the electronic control P.C. board.

• When cooling operation does not work.

1.Disconnect the lead wire leading to the compressor.

2.3 minutes after turning on the power supply, start EMERGENCY OPERATION in COOL mode.

Is there voltage of 230V AC between pin1 and

No

 

Replace the 4-way valve.

pin 2 at connector CN912? W

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

WIf the connector CN912 is not connected or R.V. coil is open, voltage occurs between terminals even when the control is OFF.

1.Turn off power supply of indoor and outdoor unit, and disconnect the connector CN781 in the outdoor electronic control P.C. board.

2.3 minutes after turning on the power supply, start EMERGENCY OPERATION in COOL mode.

Is there voltage 12V DC

No

between the connector CN781 Replace the noise filter P.C. board. pin 5 (+) and pin 3 (-)?

Yes

Replace the outdoor electronic control P.C. board.

26

Page 26
Image 26
Mitsubishi Electronics MUZ-GB50VA service manual Check of R.V. coil, When heating operation does not work