Monessen Hearth CSDV40DLP NOTE Any vent configurations within, the shaded areas are acceptable

Models: CSDV20SLP CSDV40SLP CSDV40NDV CSDV20DLP CSDV20DNV CSDV30SNV CSDV40DLP CSDV40SNV CSDV30DLP CSDV30DNV CSDV20SNV CSDV30SLP

1 44
Download 44 pages 11.36 Kb
Page 14
Image 14
Termination Clearances

CSDV Series Direct Vent Gas Stove

Venting installation

Termination Clearances

Termination clearances for buildings with combustible and noncombustible exteriors.

Inside Corner

 

 

 

 

 

G =

G

 

 

 

Combustible

 

 

 

 

 

6" (152 mm)

 

 

 

 

 

 

Figure 12 -Acceptable VentingConfigurationsVUse RestrictorNOTE: Any vent configurations withinthe shaded areas are acceptable. Minimum Height from Stove Top 18"Manual background Noncombustible 2" (51 mm)

Outside Corner

 

F =

 

 

Combustible

 

6"

(152 mm)

V

Noncombustible

2"

(51 mm)

 

 

F

 

Alcove Applications*

Manual backgroundManual background D Manual backgroundManual background

C C

V

Manual backgroundManual background E Manual background

O

Figure 12 -

Allowable

Venting

Balcony -

with no side wallManual background

M

V

M =

Combustible &

Noncombustible

12" (305 mm)

Balcony -

with perpendicular side wall

M

V

P

Combustible &

Noncombustible

M = 24" (610 mm)

P = 20” (508 mm)

584-15

E = Min. 6” (152 mm) for non-vinyl sidewalls Min. 12” (305 mm) for vinyl sidewalls

O = 8’ (2.4 m) Min.

No.

 

 

of Caps

DMin.

CMax.

 

 

 

1

3’ (914 mm)

2 x DActual

 

 

 

2

6’ (1.8 m)

1 x DActual

 

 

 

3

9’ (2.7 m)

2/3 x DActual

4

12’ (3.7 m)

1/2 x DActual

 

 

 

DMin. = # of Termination caps x 3

CMax. = (2 / # termination caps) x DActual

*NOTE: Termination in an alcove space (spaces open only on one side and with an overhang) is permitted with the dimensions specified for vinyl or non-vinyl siding and soffits. 1. There must be a 3’ (914 mm) minimum between termination caps. 2. All mechanical air intakes within 10’ (1 m) of a termination cap must be a minimum of 3’ (914 mm) below the termination cap. 3. All gravity air intakes within 3’ (914 mm) of a termination cap must be a minimum of 1’ (305 mm) below the termination cap.

 

 

40

 

 

38

 

HEIGHTVERTICAL40' MAX (12.2m) FROM(MEASUREDSTOVE TOP)

36

 

10

 

 

34

 

 

32

 

 

30

 

 

28

 

 

26

 

 

24

 

 

22

Figure 13 -

 

20

Acceptable Venting

 

18

Configurations

 

16

 

 

14

 

 

12

 

 

8

 

 

6

 

 

4

Actual Stove Height

 

2

CSDV20 = 23Z\x" (597 mm)

0

CSDV30 = 28Z\x" (724 mm)

 

CSDV40 = 30Z\x" (775 mm)

 

Use Restrictor

Disk Above

Dotted

Line

NOTE: Any vent configurations within

the shaded areas are acceptable.

Manual background Minimum Height from Stove Top 18"

Manual backgroundManual background 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

HORIZONTAL RUN 20' MAX (6.1m)

Minimum Height from Stove Top

CSDV20 = 18" (457 mm) CSDV30 = 30" (762 mm) CSDV40 = 30" (762 mm)

14

58D6056

Page 14
Image 14
Monessen Hearth CSDV40DLP manual NOTE Any vent configurations within, the shaded areas are acceptable, Venting installation

FAQ

What are the termination clearances for the CSDV series gas stoves?

The termination clearances for buildings with combustible and noncombustible exteriors are provided in the official manual. Please refer to the table for detailed information.

What is the minimum height required from the stove top for the CSDV20 model?

The minimum height required from the stove top for the CSDV20 model is 18" (457 mm).

Are there any restrictions on the allowable venting configurations?

There are no restrictions on the allowable venting configurations within the shaded areas as specified in the manual.