PRE-INSTALLATION INFORMATION

BBV, SBV Series Natural Vent Gas Fireplaces

PRE-INSTALLATION INFORMATION

FIREPLACE LOCATION

Plan for the installation of your appliance. This includes determining where the unit is to be installed, the vent configuration to be used, framing and finishing details, and whether any optional acces- sories (i.e. wall switch, or remote control) are desired. Consult your local building code agency to ensure compliance with local codes, including permits and inspections.

The following factors should be taken into consideration:

Clearance to side-wall, ceiling, woodwork and windows. Minimum clearances to combustibles must be maintained.

This fireplace may be installed along a wall, across a corner or use an exterior chase.

Location should be out of high traffic areas and away form furniture and draperies due to heat from appliance.

Never obstruct the front opening of the fireplace.

Do not install in the vicinity where gasoline or other flammable liquids may be stored.

Vent pipe routing. Refer to Venting section found in this manual for allowable venting configura- tions.

These units can be installed in a bedroom. Refer to the National Fuel Gas Code ANSI Z233.1/ NFPA 54 - (current edition), the Uniform Mechanical Code - (current edition), and Local Building Codes for specific installation requirements.

CLEARANCES TO COMBUSTIBLES

 

 

Follow these instructions carefully

 

 

to ensure safe installation. Failure to

 

 

follow instructions exactly can cre-

 

WARNING

ate a fire hazard.

 

The appliance cannot be installed on

 

 

 

 

a carpet, tile or other combustible

 

 

material other than wood flooring. If

 

 

installed on carpet or vinyl flooring,

 

 

the appliance shall be installed on a

 

 

metal, wood or noncombustible ma-

 

 

terial panel extending full width and

 

 

depth of the appliance.

 

 

 

 

 

 

 

 

 

 

 

Combustible

 

 

 

 

 

 

 

 

Mantel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72”

Side Wall

 

 

 

 

 

 

 

 

12” Maximum

Minimum

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Depth

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8” Minimum

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FIREPLACE LOCATION Minimum 3” From Both Side Walls CLEARANCES TO COMBUSTIBLES to

Opening

Figure 4 -

FP2406

Clearances

 

62D4036

Page 8
Image 8
Monessen Hearth BBV400, SBV400, SBV500 Fireplace Location, Clearances To Combustibles, Pre-Installationinformation, 62D4036