GENERAL TROUBLESHOOTING

BBV, SBV Series Natural Vent Gas Fireplaces

TROUBLESHOOTING

GENERAL TROUBLESHOOTING

 

 

 

 

 

SYMPTOM

POSSIBLE CAUSE

 

ACTION

1. Glass soots.

A. Flame impingement on

 

A. Install log set per instructions.

 

 

logs.

 

Inspect the injector and air intake area.

 

 

 

 

Make sure this area does not have any blockage from debris

 

 

 

 

and clean.

 

 

 

 

Check gas supply.

 

 

 

 

2. Poor draft due

A. Too much offset.

 

A. Reduce offset and/or raise termination.

 

to venting.

 

 

If thermocouple is producing more than 15m B, replace faulty

 

 

 

 

valve.

 

 

B. Too many elbows.

 

B. Reduce number of elbows.

 

 

C. Vent height too short.

 

C. Raise vent.

 

 

D. Vent too close to roof

 

D. Raise vent.

 

 

line.

 

 

 

 

E. Blockage is rstricting

 

E. Remove blockage.

 

 

venting capacity.

 

 

 

 

F. Incorrect vent type.

 

F. Replace with proper B-vent.

 

 

G. Venting has been con-

 

G. Replace with proper size.

 

 

structed with too large

 

 

 

 

or too small vent.

 

 

 

 

H. More than one appli-

 

H. Construct a single venting system for each appliance.

 

 

ance is using one vent-

 

 

 

 

ing system.

 

 

 

 

 

 

 

3.

Poor draft due

A. Cap obstructed by a

 

A. Remove or open enclosure or raise cap above it.

 

to termination

decorative enclosure.

 

 

 

cap.

B. Cap is crushed,

 

B. Replace cap.

 

 

damged or missing.

 

 

 

 

 

 

 

4.

Poor draft due

A. Buildings, trees, roof

 

A. Maintain proper clearances and heights to external obstruc-

 

to ext. environ-

lines interfering with

 

tions; Be aware of overhangs.

 

ment.

venting.

 

 

 

 

B. Wind

 

B. Use cap designed for high winds; raise venting height.

 

 

C. Vent exposed to cold

 

C. Insulate chase.

 

 

chase.

 

 

 

 

D. Vent exposed to cold

 

D. Enclose vent within home.

 

 

weather.

 

 

 

 

 

 

5. Poor draft due

A. Negative air pressure.

 

A. To test for negative air pressure, open a window in the room

 

to internal envi-

 

 

with the fireplace to see if the unit starts drafting correctly.

 

ronment.

 

 

Make sure the damper system is in the open position.

6.

Unit shuts down

A. Blockage or restriction

 

A. Check for and remove blockage and light pilot following light-

 

prematurely.

in venting.

 

ing instructions.

 

 

 

 

 

34

62D4036

Page 34
Image 34