DCA-220SSJ/SSJU — ENGINE OPERATING PANEL

DCA-220SSJ/SSJU — ENGINE OPERATING PANEL

The definitions below describe the controls and functions of the DCA-220SSJ/SSJU Engine Operating Panel (Figure 8).

Figure 8. Engine Operating Panel

1.Panel Light – Normally used in dark areas or at night time.When activated, panel lights will illuminate.When the generator is not in use be sure to turn the panel light switch to the OFF position.

2.Panel Light Switch – When activated will turn on control panel light.

3.Oil Pressure Gauge – During normal operation this gauge be should read between 35 to 65 psi. (241~448 kPa).When starting the generator the oil pressure may read a little higher, but after the engine warms up the oil pressure should return to the correct pressure range.

4.Water Temperature Gauge – During normal operation this gauge be should read between 180° and 230°F.(82° C and 110° C

5.Charging Ammeter Gauge – Indicates the current being supplied by the engine’s alternator which provides current for generator’s control circuits and battery charging system.

6.Fuel Gauge - Indicates amount of diesel fuel available.

7.Tachometer – Indicates engine speed in RPM’s for 50 Hz operation. This meter should indicate 1500 RPM’s when the rated load is applied. In addition a built in hour meter will record the number of operational hours that the generator has been in use.