Multiquip operation manual DCA-220SSJ/SSJU - GENERATOR CONTROL PANEL, Generator Control Panel

Models: DCA-220SSJ

1 108
Download 108 pages 30.87 Kb
Page 37
Image 37
DCA-220SSJ/SSJU — GENERATOR CONTROL PANEL

DCA-220SSJ/SSJU — GENERATOR CONTROL PANEL

Figure 7. Generator Control Panel

The definitions below describe the controls and functions of the DCA-220SSJ/SSJU Generator Control Panel (Figure 7).

1.Frequency Meter – Indicates the output frequency in hertz (Hz). Normally 50 Hz.

2.AC Ammeter – Indicates the amount of current the load is drawing from the generator per leg selected by the ammeter phase-selector switch.

3.Ammeter Change-Over Switch – This switch allows the AC ammeter to indicate the current flowing to the load connected to any phase of the output terminals, or to be switched off. This switch does not effect the generator output in any fashion, it is for current reading only.

4.Voltage Regulator Control – Allows ±15% manual adjustment of the generator’s output voltage.

5.ACVoltmeter – Indicates the output voltage present at the U,V, and W Output Terminal Lugs.

6.Voltmeter Change-Over Switch – This switch allows the AC voltmeter to indicate phase to phase voltage between any two phases of the output terminals or to be switched off.

7.Main Circuit Breaker – This three-pole, 600A main breaker is provided to protect the the U,V, andW Output Terminal Lugs from overload.

Located behind the generator control panel is the Generator Control Box. This box contains some of the necessary electronic components required to make the generator function.

The Control Box is equipped with the following major components:

Over-Current Relay

Voltage Rectifer (AVR)

Starter Relay

CurrentTransformer

Voltage Selector Switch

Three Phase Circuit Breaker

Remember the overcurrent

NOTErelay monitors the current flowing from the U,V, and W Output Terminal Lugs to the load.

In the event of a short circuit or over current condition, it will automatically trip the 600 amp main breaker.

To restore power to the Output Terminal Panel, press the reset button on the overcurrent relay and place the main circuit breaker in the closed position (ON).