4. Touch “Select” to enter the “Gage Data” display. When 8. | When the gage data has cleared, the display |
“Gage Data” is selected the PowerView will | automatically returns to the “Utilities” menu. Scroll to |
communicate with the analog gages at a fixed rate of | “Software Version”. Touch “Select” to view the software |
38.4k Band, 8 data bits, no parity check, 1 stop bits, | version currently in the diagnostic display. |
half duplex.
| SOFTWARE |
GAGE DATA | VERSION |
REMOVE ALL GAGES | MURPHY: X.XX |
SOFTWARE VERSION |
|
MODBUS SETUP |
|
FAULT CONVERSION |
|
ADJUST BACKLIGHT |
|
DEMO MODE ON |
|
5.Use the “Arrow Buttons” to scroll through the items or touch “Menu” to return to the “Utilities” menu.
9.Touch “Menu” to return to “Utilities”. Highlight Fault Conversion” using the “Arrows”.Touch “Select” to enter the Fault conversion menu.
1 of x | GAGE DATA | |
| ||
ENGINE OIL PRESSURE | REMOVE ALL GAGES | |
SOFTWARE VERSION | ||
| ||
ADDRESS:20 | FAULT CONVERSION | |
| ||
SOFTWARE REVISION #: |
| |
ERRORS: NONE |
|
6. Touch “Menu Button” to return to the “Utilities” menu. | 10. Use the “Arrows” to scroll to and highlight the desired |
| version then touch “Select”. An asterisk denotes which |
| version is currently selected. |
1 of x |
|
ENGINE OIL PRESSURE
ADDRESS:20
SOFTWARE REVISION #:
ERRORS: NONE
7.Use the “Arrows” to highlight Remove All Gages”.Touch “Select” to clear gage data from memory. It takes a moment to clear all gages.
CLEARING GAGES
PLEASE WAIT
NOTE: There are four (4) different methods for converting fault codes. The diagnostic display always looks for J1939 Version 4 and can be set to read the code as one of three (3) other J1939 versions if Version 4 is not being used. Most engine ECU’s use Version 4, therefore in most cases adjustment of this menu option will not be required.
Upon receiving an unrecognizable fault, change to a different J1939 Version. If the fault SPN does not change when the version is changed, the ECU generating the fault is using Fault Conversion method 4. If the SPN number does not change but is still unrecognizable, try changing to another J1939 Version not yet used and continue to check the SPN number.
J1939 VERSION 1
J1939 VERSION 2
J1939 VERSION 3