Multiquip DCA-220SSJ/SSJU - DIAGNOSTIC DISPLAY, When the gage data has cleared, the display

Models: DCA-220SSJ

1 108
Download 108 pages 30.87 Kb
Page 34
Image 34
When the gage data has cleared, the display

DCA-220SSJ/SSJU — DIAGNOSTIC DISPLAY

4. Touch “Select” to enter the “Gage Data” display. When 8.

When the gage data has cleared, the display

“Gage Data” is selected the PowerView will

automatically returns to the “Utilities” menu. Scroll to

communicate with the analog gages at a fixed rate of

“Software Version”. Touch “Select” to view the software

38.4k Band, 8 data bits, no parity check, 1 stop bits,

version currently in the diagnostic display.

half duplex.

 

SOFTWARE

GAGE DATA

VERSION

REMOVE ALL GAGES

MURPHY: X.XX

SOFTWARE VERSION

 

MODBUS SETUP

 

FAULT CONVERSION

 

ADJUST BACKLIGHT

 

DEMO MODE ON

 

5.Use the “Arrow Buttons” to scroll through the items or touch “Menu” to return to the “Utilities” menu.

9.Touch “Menu” to return to “Utilities”. Highlight Fault Conversion” using the “Arrows”.Touch “Select” to enter the Fault conversion menu.

1 of x

GAGE DATA

 

ENGINE OIL PRESSURE

REMOVE ALL GAGES

SOFTWARE VERSION

 

ADDRESS:20

FAULT CONVERSION

 

SOFTWARE REVISION #:

 

ERRORS: NONE

 

6. Touch “Menu Button” to return to the “Utilities” menu.

10. Use the “Arrows” to scroll to and highlight the desired

 

version then touch “Select”. An asterisk denotes which

 

version is currently selected.

1 of x

 

ENGINE OIL PRESSURE

ADDRESS:20

SOFTWARE REVISION #:

ERRORS: NONE

7.Use the “Arrows” to highlight Remove All Gages”.Touch “Select” to clear gage data from memory. It takes a moment to clear all gages.

CLEARING GAGES

PLEASE WAIT

NOTE: There are four (4) different methods for converting fault codes. The diagnostic display always looks for J1939 Version 4 and can be set to read the code as one of three (3) other J1939 versions if Version 4 is not being used. Most engine ECU’s use Version 4, therefore in most cases adjustment of this menu option will not be required.

Upon receiving an unrecognizable fault, change to a different J1939 Version. If the fault SPN does not change when the version is changed, the ECU generating the fault is using Fault Conversion method 4. If the SPN number does not change but is still unrecognizable, try changing to another J1939 Version not yet used and continue to check the SPN number.

J1939 VERSION 1

J1939 VERSION 2

J1939 VERSION 3

PAGE 34 — DCA-220SSJ/SSJU— OPERATION AND PARTS MANUAL — REV. #1 (01/06/09)

Page 34
Image 34
Multiquip DCA-220SSJ/SSJU - DIAGNOSTIC DISPLAY, When the gage data has cleared, the display, half duplex