Outdoor Installation

Install the generator in a location where it will not be exposed to rain or sunshine. Make sure the generator is on secure level ground so it cannot slide or shift around. Also install the generator so the exhaust will not be discharged in the direction of nearby homes.

The installation site must be relatively free from moisture and dust. All electrical equipment should be protected from excessive moisture. Failure to do will result in deterioration of the insulation and will result in short circuits and grounding.

Foreign materials such as dust, sand, lint and abrasive materials have a tendency to cause excessive wear to engine parts and alternator.

CAUTION :

Pay close attention to ventilation when operating the generator inside tunnels and caves. The engine exhaust contains noxious elements. Engine exhaust must be routed to a ventilated area.

Indoor Installation

Exhaust gases from diesel engines are extremely poisonous. Whenever an engine is installed indoors the exhaust fumes must be vented to the outside.The engine should be installed at least two feet from any outside wall. Using an exhaust pipe which is too long or too small can cause excessive back pressure which will cause the engine to heat excessively and possibly burn the valves.

Table of Contents

DCA-220SSK — INSTALLATION

CAUTION :

An electric shock may happen when vibrators are used. Pay close attention to handling when operating vibrators and always use rubber boots and gloves to insulate the body from electrical shock.

Generator Grounding

To guard against electrical shock and possible damage to the equipment, it is important to provide a good EARTH ground.

Article 250 (Grounding) of the National Electrical Code (NEC) provides guide lines for proper grounding and specifies that the cable ground shall be connected to the grounding system of the building as close to the point of cable entry as practical.

NEC articles 250-64(b) and 250-66 set the following grounding requirements:

1.Use one of the following wire types to connect the generator to earth ground.

a.Copper - 10 AWG (5.3 mm2) or larger.

b.Aluminum - 8 AWG (8.4 mm2) or larger.

2.When grounding the generator (Figure 39) connect the ground cable between the lock washer and the nut on the generator and tighten the nut fully. Connect the other end of the ground cable to earth ground.

3.NEC article 250-52(c) specifies that the earth ground rod should be buried a minimum of 8 ft. into the ground.

NOTE

When connecting the generator to any buildings electrical system ALWAYS consult with a licensed electrician.

PAGE 42 — DCA-220SSK — PARTS AND OPERATION MANUAL (STD) — REV. #3 (06/05/01)

Page 42
Image 42
Multiquip operation manual DCA-220SSK Installation, Outdoor Installation, Indoor Installation

DCA-220SSK specifications

The Multiquip DCA-220SSK is a robust and versatile generator designed to meet the diverse demands of construction sites, rental facilities, and emergency backup needs. This generator stands out with its ability to deliver reliable power in a compact and easy-to-transport package.

At the heart of the DCA-220SSK is a powerful water-cooled, 4-cylinder diesel engine that provides a rated output of 220 kVA. This engine is coupled with a heavy-duty alternator that ensures an efficient and stable power supply, making it suitable for a wide range of applications. The generator features a sound-attenuated enclosure, designed to minimize noise levels and enhance mobility. This encasement not only protects the inner components from harsh environmental conditions but also complies with strict noise regulations, making it a great choice for urban job sites.

One of the key features of the DCA-220SSK is its advanced digital control panel, which offers intuitive monitoring and management of the generator's operation. This panel allows users to easily track essential performance metrics such as voltage, frequency, and hour count, ensuring optimal functionality. Furthermore, it is equipped with several safety features, including low oil pressure and high temperature shutdowns, which protect the unit from damage and extend its lifecycle.

In terms of fuel efficiency, the DCA-220SSK is designed to operate at a low fuel consumption rate, making it cost-effective for long-term use. Additionally, its large fuel tank provides extended runtime, enhancing productivity by reducing the frequency of refueling.

The generator's compact design is complemented by heavy-duty wheels and lifting points, facilitating ease of transportation and deployment in various job settings. This rugged design is ideally suited for construction, industrial use, and other commercial applications, where reliability and performance are paramount.

Ultimately, the Multiquip DCA-220SSK delivers high-quality power with its innovative technology and features that cater to the needs of end users seeking durability, efficiency, and reliability in their power solutions. Whether for temporary power at a construction site or as a dependable backup during emergencies, this generator is a commendable choice in the competitive landscape of commercial power equipment.