DCA-25USI — GAUGE READING/TERMINAL PANEL CONNECTIONS

The gauges and selector switches on the control panel DO NOT effect the generator output. They are provided to help observe how much power is being supplied at the Output terminals lugs.

Before taking a reading from either gauge, set the Voltage Selector Switch (Figure 16) to the position which produces the required voltage (For example, for 3Ø 240V, choose the center 3Ø 240/139V position on

the voltage selector switch.)

Figure 16. Voltage Selector

Switch 240/139V Three Phase

Position

Reading Amperage

To determine the amperage at a terminal lug, set the AC Ammeter Change-Over Switch to the appropriate setting (Figure 19) to activate the AC Ammeter Gauge (Figure 20 and read the available amperage at the termi- nal lug.

For example, to measure the amperage at the U terminal lug, set the AC Ammeter Change-Over Switch to U and read the AC Ammeter Gauge.

NOTE

Reading Voltage

For 3Ø 208V/1Ø,120V, place the Voltage Selector Switch in the 3 Phase 240/139 position.

Figure 19. AC Ammeter

Change-Over Switch

NOTE

Figure 20. AC Ammeter (Amp reading on U lug)

The ammeter gauge will only show a reading when the Output Terminal Lugs are connected to a load and in use.

To determine the voltage between two terminal lugs, set the AC Voltmeter Change-Over Switch to the appropriate setting (Figure 17) to activate the AC Voltmeter Gauge (Figure 18) and read the available voltage between the two lugs.

For example, to measure the voltage between the W and U terminal lugs, set the AC Voltmeter Change-Over Switch to W-U and read the AC Voltmeter Gauge.

Figure 17. AC Voltmeter

Figure 18. AC Voltmeter

Change-Over Switch

Gauge

 

(Volt reading on W-U Lug)

DCA-25USIXF/DCA-25USI2XF — OPERATION AND PARTS MANUAL — REV. #1 (05/08/09) — PAGE 27