UVWO Terminal Output Voltages

DCA-25USIXF/DCA-25USI2XF— OUTPUT TERMINAL PANEL

UVWO Terminal Output Voltages

Various output voltages can be obtained using the Output Terminal Lugs. The voltages at the terminals are depen- dent on the position of the Voltage Selector Switch and the adjustment of the Voltage Regulator Control Knob.

Remember the voltage selector switch determines the range of the output voltage. The voltage regulator (VR) allows the user to increase or decrease the selected voltage.

3Ø 240/139 Output Terminal Lug Voltages

1.Place the voltage selector switch in the 3Ø 240/139 position as shown in Figure 21.

Figure 21. Voltage Selector Switch 240/139V

Three-Phase Position

2.Connect the load wires to the OutputTerminal Lugs as shown in Figure 22.

3Ø 208V/1Ø120V Output Terminal Lug Voltages

1.Place the voltage selector switch in the 3Ø 240/139 position as shown in Figure 24.

Use this position for 3Ø-240 or 1Ø120V.

Figure 24. Voltage Selector

Switch 240/139V

Three-Phase Position

2.Connect the load wires to the OutputTerminal Lugs as shown in Figure 25.

Figure 25. Output Terminal Lugs

3Ø-208/120V Connections

3.Turn the voltage regulator knob (Figure 23) clockwise to increase voltage output, turn counterclockwise to decrease voltage output.

Figure 22. Output Terminal Lugs

 

To achieve a 3Ø 208V output

 

the voltage selector switch

3Ø-240/139V Connections

NOTE

must be in the 3Ø-240/139

3. Turn the voltage regulator knob (Figure 23) clockwise to

 

position and the voltage

increase voltage output, turn counterclockwise to

 

regulator must be adjusted to

decrease voltage output.

 

208V.

Figure 23. Voltage Regulator Knob (139V/240V)

PAGE 28 — DCA-25USIXF/DCA-25USI2XF — OPERATION AND PARTS MANUAL — REV. #8 (05/08/09)