Single Phase Load

DCA-25SSIU — LOAD APPLICATION

CAUTION:

Always be sure to check the nameplate on the generator and equipment to insure the wattage, amperage and frequency requirements are satisfactorily supplied by the generator for operating the equipment.

Generally, the wattage listed on the nameplate of the equipment is its rated output. Equipment may require 130— 150% more wattage than the rating on the nameplate, as the wattage is influenced by the efficiency, power factor and starting system of the equipment.

When the voltage selector switch is in single phase (240/ 120V position), place the AC voltmeter change-over switch to the U-W position and the AC ammeter change over-switch to the U or W position to read the output.

NOTE

If wattage is not given on the equipment's name plate, approximate wattage may be determined by multiplying nameplate voltage by the nameplate amperage.

WATTS = VOLTAGE x AMPERAGE

The power factor of this generator is 1.0. See Table 13. below when connecting loads.

Table 13. Power Factor By Load

Type Of Load

Power Factor

 

 

Single-phase induction motors

0.4 - 0.75

 

 

Electric heaters, incandescent

1.0

lamps

 

 

 

Fluorescent lamps, mercury lamps

0.4 - 0.9

 

 

Electronic devices, communication

1.0

equipment

 

Common power tools

0.8

 

 

Three Phase Load

When calculating the power requirements for 3-phase power use the following equation:

Motors and motor-driven equipment draw much greater current for starting than during operation.

An inadequate size connecting cable which cannot carry the required load can cause a voltage drop which can burn out the appliance or tool and overheat the cable.

When connecting a resistance load such as an incandescent lamp or electric heater, a capacity of up to the generating set’s rated output (kW) can be used.

When connecting a fluorescent or mercury lamp, a capacity of up to the generating set’s rated output (kW) multiplied by 0.6 can be used.

When connecting an electric drill or other power tools, pay close attention to the required starting current capacity.

If wattage is not available on the equipment, approximate wattage may be determined by multiplying the nameplate voltage by the nameplate amperage for three-phase:

WATTS =1.732 x VOLTAGE x AMPERAGE

CAUTION:

Before connecting this generator to any building’s electrical system, a licensed electrician must install an isolation (transfer) switch. Serious injury or death may result without this transfer switch.

NOTE

If output (kVA) is not given on the equipment nameplate, approximate output may be determined by multiplying voltage by

amperage by and 1.732.

PAGE 42 — DCA-25SSIU — PARTS AND OPERATION MANUAL(STD) — REV. #7 (04/18//12)

Page 42
Image 42
Multiquip DCA25SSIU manual DCA-25SSIU Load Application, Single Phase Load, Three Phase Load