DCA-25SSIU — GENERAL INFORMATION
DCA-25SSIU FAMILIARIZATION
Generator
The MQ Power Model
Engine Operating Panel
The “Engine Operating Panel” is provided with the following:
Tachometer
Water Temperature Gauge
Oil Pressure Gauge
Charging Ammeter Gauge
Fuel level gauge
Engine Throttle Lever
Alarm Lights
Panel Light
Panel Light Switch
Starter Switch
Generator Control Panel
The “Generator Control Panel” is provided with the following:
Output Voltage Adjustment Knob
Frequency Meter (Hz)
AC Ammeter (Amps)
AC Voltmeter (Volts)
Ammeter
Voltmeter
Main Circuit Breaker 60 amps
Output Terminal Panel
The “Output Terminal Panel” is provided with the following:
Three 120V output receptacles, 50 amp
Two 120V output receptacles, 20 amp
3 Circuit Breakers 240V @65 amps
2 GFCI Circuit Breakers 120V@ 20amps
Open Delta Excitation System
The
There are four leads: A, B, C and D. During light loads, the power to the AutomaticVoltage Regulator (AVR) is supplied from the leads parallel connections of B&C. When loads increase, the AVR switches and accepts power from leads A&D. The output of leads A&D increase proportionally with load. This of adding the voltages to each phase provides better voltage response during heavy loads.
The connections of the AVR to the AC output windings are for sensing only. No power is required from these windings.
The
Engine
The
In keeping with MQ Power’s policy of constantly improving its products, the specifications quoted herein are subject to change without prior notice.
The basic controls and indicators for the
Mechanical Governor System
The mechanical governor system control the RPM of the engine. When the engine demands increase or decrease, the mechanical governor system regulates the frequency to ±5%. The electronic governor option limits frequency fluctuation to ±0.25%.