DCA-25USIXF/DCA-25USI2XF— GENERATOR START-UP PROCEDURE

8.The engine oil pressure gauge (Figure 48) will indicate the oil pressure of the engine. Under normal operating conditions the oil pressure is approximately 28~71 psi (193~490 kPa).

Figure 48. Oil Pressure Gauge

9.The coolant temperature gauge (Figure 49) will indicate the coolant temperature. Under normal operating conditions the coolant temperature is between 165°~203° F. (74°~95° C).

11.Turn the main, GFCI, and aux. circuit breakers to the ON position (Figure 51).

Figure 51. Main, AUX. and GFCI

Circuit Breakers (ON)

12.Observe the generator's ammeter (Figure 52) and verify it reads the anticipated amount of current with respect to the load. The ammeter will only display a current reading if the load is in use.

Figure 49. CoolantTemperature Gauge

10.The tachometer (Figure 50) will indicate the speed of the engine when the generator is operating. Under normal operating conditions this speed is approximately 1800 RPM’s.

Figure 52. Ammeter (Load)

13.The generator will run until manually stopped or an abnormal condition occurs.

Figure 50. Engine Tachometer

PAGE 36 — DCA-25USIXF/DCA-25USI2XF — OPERATION AND PARTS MANUAL — REV. #8 (05/08/09)