DCA-40SSAI — OUTPUT AMPERAGE SETUP

Output Terminal Panel Available Voltages

A wide range of voltages are available to supply load to many different applications. Voltages may be selected by using the voltage selector switch and depending how you hookup your hard wire connection to the generator. To obtain some of the voltages listed, fine adjustment with the voltage regulator on the control panel is necessary. See Table 8 for available voltages the generator will supply.

Over Current Relay

An over current relay is connected to the circuit breaker. During an over current situation, both the circuit breaker and the over current relay will trip. If the circuit breaker can not be reset, the reset button on the over current relay must be pressed. The over current relay is located inside the control box.

Table 8. Voltages Available

Three Phase

208 VOLT

220 VOLT

240 VOLT

416 VOLT

440 VOLT

480 VOLT

(Switchable)

 

 

 

 

 

 

 

 

 

 

 

 

 

Single Phase

120 VOLT

127 VOLT

139 VOLT

240 VOLT

254 VOLT

277 VOLT

(Switchable)

 

 

 

 

 

 

 

 

 

 

 

 

 

CAUTION :

NEVER switch Voltage Selector Switch position while the engine is engaged.

Maximum Amps

Table 9 shows the maximum amps the generator will pro- vide. Do not exceed the maximum amps listed.

Voltage Selector Switch Locking Button

The voltage selector switch has a locking button to protect the generator and generator load from being switched while the engine is running. To lock the voltage selector switch, press in the red button located on the voltage selector switch, and use a pad lock to hold it into this position.

Table 9. Maximum Amps

Rated

Maximum Amps

Voltage

 

 

 

Single Phase

100 amps (4 wire)

120 Volt

 

 

 

Single Phase

50 amps (4 wire)

240 Volt

 

 

 

Three Phase

108 amps

240 Volt

 

 

 

Three Phase

54 amps

480 Volt

 

 

 

PAGE 34 — DCA-40SSAI — PARTS AND OPERATION MANUAL — FINAL COPY (07/09/01)

Page 34
Image 34
Multiquip operation manual DCA-40SSAI Output Amperage Setup