DCA-40SSAI — OUTPUT AMPERAGE SETUP

Receptacle Use

When the UVWO terminals are providing power, the recep- tacle power availability will decrease. Do not exceed recep- tacle power as listed on Table 10.

Table 10. Receptacle Use

 

 

Receptacle

Power in Use

Power

 

 

Available

 

 

 

 

240/120V

Duplex

240/480V

Single Phase

NEMA

3-Phase

or Twist

5-20R 120V

 

Lock CS6369

 

 

 

 

 

KVA

KW

KW

 

 

 

45

26

0

 

 

 

40.9

24.8

1.2

 

 

 

36.7

23.6

2.4

 

 

 

32.6

22.4

3.6

 

 

 

28.4

21.2

4.8

 

 

 

How To Read The Output Terminal Gauges.

The gauges (Figure 15 and 17) and change-over switches on the control panel DO NOT effect the generator output. They are to help observe how much power is being supplied at the UVWO legs.

When the voltage selector switch is in the 240/120V posi- tion (Figure 13), place the AC voltmeter change-over switch to the W-U position (Figure 14) and the AC ammeter change- over switch to the U or W position (Figure 16) to read the output on the selected leg.

Figure 13. Voltage Selector Switch 240/120V Single

Phase Position

Figure 14 and 15. AC Voltmeter Change-over switch

and Voltmeter Gauge

40

2060

0

75

A

Figure 16 and 17. AC Ammeter Change-over Switch

and Ammeter Gauge

NOTE

When using plural single phase voltages, make sure to balance the load on each of the single phase legs.