DCA-40SSAI — GENERATOR SHUTDOWN PROCEDURE

ENGINE SHUTDOWN

To shutdown the generator, use the following procedure:

1.Switch both the MAIN, GFCI and LOAD circuit breakers (Figure 52) to the “OFF” position.

EMERGENCY STOP

1.To stop the engine in the event of an emergency, switch the MAIN, GFCI and LOAD circuit breakers to ‘OFF’ position.

2.Turn the starter switch key to ‘Stop’ position.

Figure 52. Main, GFCI and Load circuit breakers

2.Turn and push the engine throttle control lever (Figure

53)to the idle (low) position.

Figure 53. Engine Throttle Control Lever

3.Let the engine cool by running it for 3-5 minutes with no load applied.

4.Turn the starter switch key to ‘Stop” position (Figure 54).

Figure 54. Off/Manual Auto Switch

5.Remove the load from the UNV terminal strip.