![](/images/new-backgrounds/1041925/4192553x1.webp)
ST-45 PUMP — OPERATING PROCEDURES
D.Carefully knock the end of the hose away from the reducer.
E.Chip the concrete out of the reducer with the pry bar.
F. Remove the reducer. From the discharge end, chip the concrete out of the shuttle tube with the
G.The senior operator may then remove the inspection cover plate from the shuttle tube by using a long extension wrench and the 24" pry bar.
WARNING
Make sure the accumulator pressure gauge reads ZERO psi. prior to performing any maitinance or inspection.
H.Chip the blockage out with the
I.Flush the shuttle tube with water.
J.Replace and seal the inspection cover plate on the shuttle tube.
K.Before resuming operation of the pump, perform the “Reverse” Pumping Procedure to relieve pressure on the shuttle tubes.
17.If it is necessary to wait 1/2 hour or more for another load of concrete, and to prevent setting of the mix in the system, it is advisable to consider the following factors (A through D) affecting the concrete :
A.How old is the concrete?
B.Is there an accelerator, calcium chloride, red label, etc., in the concrete?
C.The temperature of the day, 80, 90, degrees?
D.Howmuchsystemyouhaveoutandhowstiffwasthemix you were pumping?
NOTE | When disconnecting hoses, use | |
EXTREME CAUTION! The hose is | ||
| ||
| under pressure! |
If, for any reason, the mix should set up in the system, the following procedure (E through H) is suggested:
E.Disconnectthehosefromthepumpandwashthepump out immediately.
F.Reconnect the hose and fill the hopper with water.
G.Reconnect the hose and fill the hopper with water.DO NOT try to push all the concrete out of all of the hose lines at one time.
Forexample:Ifyouhad200ft.ofsystemout,youwould disconnect each hose. Clean it out by pushing water through the first hose off the pump, then continue progressing through all the hoses, until all the system is clean.
H.Ifwaitingtimeisexcessive,itwouldbewisetowashout the pump and hoses and start over when the new truck arrives.This can be avoided by being observant to the pump and system, also taking into consideration the above factors (E through H) affecting the mix.
18.
Thereasonforusingthewetspongeistokeeptheslurryfrom running too far ahead of the concrete and so reducing the possibility of separation. When the pump is stopped, the material can flow slowly down, due to gravity, and cause the hose to collapse.
When pumping is resumed, you can expect blockage at the point of hose collapse.To prevent this from happening, the hosecanbe“kinkedoff”atthedischargeendwhenthepump is stopped to prevent the gravity flow of the material in the hose.
The use of stiffer mixes when pumping
19.VerticalPumping– When pumpingverticallyup thesideof a building, above 40 feet, we would recommend the instal- lationofsteelpipesecurelyfastenedatintervalsasnecessary to support the pipe.Ninety degree, long radius pipe sweeps should be installed at the top and bottom of the steel line.
MAYCO