10
TOP EXIT / HORIZONTAL TERMINATION
|
|
| ||
(HT) > (VT) |
| Example 2: | ||
|
| |||
Simple venting configuration | FIGURE 9 | V1 | = VT | = 6 ft |
(only one 90° elbow) | H1 | = 3 ft | ||
|
| H2 | = 5 ft | |
|
| HR | = H1 | + H2 = 3 + 5 = 8 ft |
|
| HO | = .03(two 90° elbows - 90°) = .03(180° - 90°) = 2.7 ft | |
|
| HT | = HR + HO = 8 + 2.7 = 10.7 ft | |
|
| HT | + VT= 10.7 + 6 =16.7 | |
|
| Formula 1: | HT < 4.2 VT | |
|
|
|
| 4.2 VT = 4.2 x 6 = 25.2 ft |
|
|
|
| 10.7 < 25.2 |
Formula 2: HT + VT < 24.75 feet 16.7 < 24.75
Since both formulas are met, this vent configuration is ac- ceptable.
Example 3:
See graph to determine the required vertical rise VT for the |
|
|
| H3 | ||||||
required horizontal run HT. |
|
|
|
|
|
|
| |||
| 150 |
|
|
|
|
|
|
| 90° | |
REQUIRED | 140 |
|
|
|
|
|
|
| H4 | |
VERTICAL | 130 |
|
|
|
|
|
|
| V2 | |
RISE IN | 120 |
|
|
|
|
|
|
| ||
INCHES | 110 |
|
|
|
|
|
|
|
| |
VT |
|
|
|
| V1 | H1 | H2 | |||
100 |
|
|
|
| ||||||
|
|
|
|
| ||||||
|
| 90 |
|
|
|
|
|
|
|
|
|
| 80 |
|
|
|
|
|
|
|
|
|
| 70 |
|
|
|
|
|
|
| FIGURE 11 |
|
| 60 |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| |
|
| 50 |
|
|
|
|
|
|
|
|
|
| 40 |
|
|
|
|
|
|
|
|
|
| 30 |
|
|
|
| V1 |
| = 4 ft |
|
|
| 20 |
|
|
|
| V2 |
| = 1.5 ft |
|
|
| 10 |
|
|
|
| VT |
| = V1 + V2 = 4 + 1.5 = 5.5 ft | |
|
| 0 | 5 | 10 | 15 | 20 | H1 |
| = 2 ft |
|
|
| H |
| = 1 ft |
| |||||
HORIZONTAL VENT RUN PLUS OFFSET IN FEET HT |
|
| ||||||||
H32 |
| = 1 ft |
| |||||||
The shaded area within the lines represents acceptable | H4 |
| = 1.5 ft |
| ||||||
values for HT and VT . |
|
|
|
| HR |
| = H1 + H2 + H3 + H4 = 2 + 1 + 1 + 1. 5 = 5.5 ft | |||
|
|
|
|
|
|
| HO |
| = .03(four 90° elbows - 90°) = .03(360° - 90°) = 8.1 ft | |
For vent configurations requiring more than one 90° elbow | HT |
| = HR + HO = 5.5 + 8.1 = 13.6 ft | |||||||
the following formulas apply: |
|
|
|
| HT | + VT = 13.6 + 5.5 = 19.1 ft | ||||
Formula 1: HT | < 4.2 VT |
|
|
|
| Formula 1: HT | < 4.2 VT | |||
Formula 2: HT | + VT < 24.75 feet |
|
|
|
|
| 4.2 VT = 4.2 x 5.5 = 23.1 ft | |||
|
| 90° |
|
|
|
|
|
| 13.6 < 23.1 | |
|
|
|
|
|
| Formula 2: HT | + VT < 24.75 feet | |||
|
|
|
|
|
|
|
|
| 19.1 < 24.75 |
|
|
|
|
|
V | 1 | H1 | H2 | Since both formulas are met, this vent configuration is |
|
|
| FIGURE10 | acceptable. |
|
|
|
|