Napoleon Fireplaces GDS26P Venting Application Flow Chart, Stove Vent Exit, Rear Exit, Top Exit

Models: GDS26P GDS26N

1 32
Download 32 pages 20.19 Kb
Page 8
Image 8
VENTING APPLICATION FLOW CHART

W415-0607 / A / 01.18.08

8

VENTING APPLICATION FLOW CHART

STOVE VENT EXIT

 

 

REAR EXIT

 

 

 

 

 

TOP EXIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Horizontal Termination

Vertical Termination

Horizontal Termination

Vertical Termination

Vertical rise is equal to or greater t h a n t h e horizontal run

Horizontal run + verti- cal rise to maximum of 40 feet

Vertical rise is less than horizontal run

Horizontal run + verti- cal rise to maximum of 24.75 feet

3.5times the vertical rise equal to or greater than the horizon- tal run

Vertical rise is equal to or greater t h a n t h e horizontal run

Horizontal run + verti- cal rise to maximum of 40 feet

Vertical rise is less than horizontal run

Horizontal run + verti- cal rise to maximum of 40 feet

3times the vertical rise equal to or greater than the horizon- tal run

Vertical rise is equal to or greater t h a n t h e horizontal run

Horizontal run + verti- cal rise to maximum of 40 feet

Vertical rise is less than horizontal run

Horizontal run + verti- cal rise to maximum of 24.75 feet

4.2times the vertical rise equal to or greater than the horizon- tal run

Vertical rise is equal to or greater t h a n t h e horizontal run

Horizontal run + verti- cal rise to maximum of 40 feet

Vertical rise is less than horizontal run

Horizontal run + verti- cal rise to maximum of 40 feet

3 times the vertical rise equal to or greater than the horizon- tal run

Page 8
Image 8
Napoleon Fireplaces GDS26P Venting Application Flow Chart, Stove Vent Exit, Rear Exit, Top Exit, Horizontal Termination