5
|
|
|
| DIMENSIONS | ||||
|
|
|
| |||||
FIGURE 1a | FIGURE 1b |
|
|
|
| FIGURE 1c | ||
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
23 | 5/8” |
4” DIA. | 7” DIA. |
35 | 1/2” | 29 1/8” |
|
37”
GAS
LINE
ACCESS
18 1/8” | ELECTRICAL |
| ACCESS |
VENTING
VENTING LENGTHS AND AIR TERMINAL LOCATIONS
Use only Wolf Steel, Simpson
All outer pipe joints of these venting systems must be sealed using Red RTV High Temperature Sealant.
The connection between the adaptor for these systems and the stove flue collar must be sealed using the black high temperature sealant Mill Pac (not supplied).
A starter adaptor must be used with the following vent systems and may be purchased from the corresponding supplier:
PART | 4"/7" | SUPPLIER |
Duravent | GDS924N | Wolf Steel |
Amerivent | American Metal | |
Direct Temp | Selkirk |
For Simpson
VENTING SUPPLIER | WEBSITE ADDRESS |
Simpson | www.duravent.com |
Selkirk Direct Temp | www.selkirkcorp.com |
American Metal Amerivent | www.americanmetalproducts.com |
For vent systems that provide seals on the inner exhaust flue, only the outer air intake joints must be sealed using a red high temperature silicone (RTV). This same sealant
may be used on both the inner exhaust and the outer intake vent pipe joints of all other approved vent systems except for the exhaust vent pipe connection to the stove flue collar which must be sealed using the black high temperature sealant Mill Pac.
When using Wolf Steel venting components, use only approved Wolf Steel rigid / flexible components with the following termination kits:Wall Terminal Kit GD222, or 1/12 to 7/12 Pitch Roof Terminal Kit GD110, 8/12 to 12/12 Roof Terminal Kit GD111, Flat Roof Terminal Kit GD112 or Periscope Kit GD201 (for wall penetration below grade).
Also approved for use with Duravent's
The maximum allowable vertical vent length is 40 feet, the minimum allowable vertical vent length is 3 feet. For optimum flame appearance and stove performance, keep the vent length and number of elbows to a minimum. The air terminal must remain unobstructed at all times. Examine the air terminal at least once a year to verify that it is unobstructed and undamaged.
Horizontal runs may have a 0" rise per foot in all cases using Wolf Steel, Simpson
For optimum performance, it is recommended that horizontal runs have a minimum 1" rise per foot when using Simpson
Wolf Steel, Simpson
VENT INSTALLATIONS
For safe and proper operation of the stove follow the venting instruction exactly.
Deviation from the minimum or the maximum vertical vent length can create difficulty in burner
Vent lengths that pass through unheated spaces (attics, garages, crawl spaces) should be insulated with the insulation wrapped in a protective sleeve to minimize condensation.
Use a firestop, vent pipe shield or attic insulation shield when penetrating interior walls, floor or ceiling.
FOR SPECIFIC VENTING PARAMETERS, REFER TO PAGES