1.6Installation requirements for mains power connection

The power system of the DELTABOOSTER is designed in conformity with the common Euro- pean standard:

EN 60204-1 (October 1992): Electrical equipment of machines, Part 1: General requirements.

Power should be connected through a flexible rubber cable holding copper conductors for 3 phases and earth (PE).The minimum dimensions of the cable are determined by the power consumption of the current system (cf. data sheet), but common to all systems is the following:

Max pre-fuse:

125

A

Max core section of cable:

35

mm

In consideration of a future extension of the plant we recommend you to use a cable with a min. core section of cable of 25 mm.

Earth wire protection is required and the connection of the DELTABOOSTER to the mains power supply MUST be carried out by an authorized electrician in conformity with local regulations. To ensure maximum protection of persons, the installation should be protected by a Residual Current Device (RCD).

PE L1 L2 L3

Ground fault circuit interrupter

SUPPLY NETWORK

max 125 A

max 35

PE

DELTABOOSTER control system