CONFIGURATION PROCEDURE
CONFIGURATION KEY FUNCTIONS
RESET | In Configuration Mode, it is used only to scroll | |
| back parameters without to memorize a new | |
| parameter value. | |
| Used in Configuration Mode to decrease the | |
| parameter value. | |
| Used in Configuration Mode to increase the | |
| parameter value. | |
FUNC | Used to memorize the new parameter | |
| value and go to the next parameter. | |
+ | Loads the default parameters. | |
+ FUNC or | + FUNC | |
| Increases/decreases values at a higher rate | |
| when modifying parameters. | |
+ RESET or | + RESET | |
| Jumps to the Maximum or Minimum param- | |
| eter value when modifying parameters. |
CONFIGURATION PROCEDURE
1)Remove the instrument from its case.
2)Open switch V101 (See illustrations under “Preliminary Hardware Settings.”)
3)
4)Switch on power to the instrument. The upper display will show COnF.
NOTE : If "CAL" indication is displayed, press
immediately the pushbutton and return to the configuration procedure.
5)Press the “” key and the lower display will show the firmware version.
Press the "FUNC" key to start the configuration procedure with the first parameter (L1).
The following is a complete list of parameters. The lower display will show the parameter code (L1 to d1) and the upper display will show the selection code or numerical value. No timeout is applied in the configuration mode.
L 1 | = | Serial Interface Protocol |
(Skipped if option is not available.) | ||
OFF | = | No serial interface |
nbUS = | Modbus | |
jbUS = | Jbus |
L 2 = Serial Link Device Address (Skipped if option is not available or L1 = OFF) From 1 to 255
NOTE: EIA standard allows no more than 31 device connected by one
L 3 = Baud Rate for Serial Link (Skipped if option is not available or L1 = OFF) Set value from 600 to 19200 baud.
(19200 baud is shown on display as 1920)
L 4 = Byte Format for Serial Link (Skipped if option is not available or L1 = OFF) 8E = 8 bits + even parity
8O = 8 bits + odd parity
8 = 8 bits without parity
9
9 | 19/04/2004, 15.07 |