Indicators
“RESET“ =Indicates control output 1 status as follows:
a)When C2 parameter has been configured equal to 0,
LED ON when Output 1 is OFF LED OFF when Output 1 is ON
b)When C2 parameter has been configured equal to 1,
LED flashes when Output 1 is OFF
LED ON when Output 1 is OFF and acknowledged
LED OFF when Output is ON “ALM” = Indicates alarm status as follows:
-Flashes when alarm is ON
-ON when alarm has been resetted but the alarm condition is still present.
-OFF when alarm is OFF
“REM” = Indicates the remote status of the instrument.
-Flashes when instrument is in remote mode.
-OFF when instrument is in local mode.
Key Functions in Normal Display Mode “FUNC” = By pressing it, the display changes from
“Normal Display Mode” to “Operative Parameter Display Mode.”
=Pressing it for more than ten seconds initiates the Lamp Test. During the Lamp Test the device function normally while all display segments and LED's are lit with a 50% duty cycle. No timeout is applied to a lamp test.
Press the "FUNC" key again to end the Lamp Test.
"" or “
" = By pressing these keys it is possible to change the displayed information. See “Normal Display Mode” on previous page.
“RESET” = Press and hold for 1 second to rearm (reset) the limiter.
+ FUNC or
+ FUNC
Increases/decreases values at a higher rate when modifying parameters.
+ RESET or
+ RESET
Jumps to the Maximum or Minimum parameter value when modifying parameters.
Operative Parameter Display Mode
The "FUNC" key initiates the Operative Parameter Display Mode when pressed for less than 10 seconds in the "Normal Display Mode."
The lower display shows the parameter code while the upper display shows the parameter value or status. The value of the selected parameter can be modified with the and
keys.
Press the "FUNC" key again to store the new value and advance to the next parameter.
If no keys are pressed within the timeout period (see t1), the instrument will automatically return to the "Normal Display Mode" in the previous display and any modification of the last displayed parameter will be lost.
All parameters (except a 6) can be modified only when the device is UNLOCKed.
The LOCK/UNLOCK status can be selected in configuration using “n1” parameter or during the operating mode with the “nn” parameter (pass- word).