STANDARD RANGES TABLE
| Input | type |
| impedance | Accuracy | |||
|
|
|
|
|
| |||
15 |
| 0 - 60 mV | > 1 MΩ |
|
| |||
16 |
| 12 | - 60 mV |
|
| |||
|
|
|
| |||||
17 |
| 0 - 20 mA | < 5 Ω |
|
| |||
18 |
| 4 - 20 mA | 0.2 % | + 1 digit | ||||
|
| |||||||
19 |
| 0 | - | 5 V | > 400 kΩ | @ 25°C | ||
20 |
| 1 | - | 5 | V | (77 | °F) | |
|
| |||||||
21 |
| 0 | - 10 | V | > 400 kΩ |
|
| |
22 |
| 2 | - 10 | V |
|
| ||
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
D) LOGIC INPUTS
(for models with RS-485 only)
This instrument is provided of 1 logic input used for remote acknowledgement.
NOTES
1)Use an external dry contact capable of switching 0.5 mA, 5 V DC.
2)The instrument needs 100 ms to recognize a contact status variation.
3)The logic inputs are NOT isolated by the measuring input.
OUTPUTS
Output updating time :
-250 ms when a linear input is selected
-500 ms when a TC or RTD input is selected.
OUTPUT 1
Type: relay SPDT contact .
Contact rated: 3 A at 250 V AC on resistive load.
Function: Safety limiter output.
Action: reverse
OUTPUT 2
Type: relay SPST contact .
Contact rated: 2 A at 250 V AC on resistive load.
Function: Alarm output
Action: direct/reverse programmable by front keyboard.
ALARM
Action: Direct or reverse acting.
Alarm functions: configurable as process alarm, band alarm or deviation alarm.
Alarm reset: automatic reset, manual reset or "Silence" function is programmable.
Stand by (mask) alarm: the alarm can be configured with or without stand by (mask) function.
Process alarm:
Operative mode : High or low programmable.
Threshold : programmable in engineering unit within the readout span.
Hysteresis: programmable from 0.1 % to 10.0 % of the readout span.
23
23 | 19/04/2004, 15.07 |