12.4.2Horizontal Airflow

12.4.2Horizontal Airflow

The horizontal airflow direction louvers can be adjusted manually by hand.

12.5Quiet Operation (Cooling Mode/Cooling Area of Dry Mode)

šPurpose

o To provide quiet cooling operation compare to normal operation.

šControl condition

oQuiet operation start condition

ƒWhen “Quiet” button at remote control is pressed. Quiet LED illuminates.

oQuiet operation stop condition

ƒWhen one of the following conditions is satisfied, quiet operation stops:

šPowerful button is pressed.

šStop by OFF/ON button.

šOFF Timer activates.

šQuiet button is pressed again.

ƒWhen quiet operation is stopped, operation is shifted to normal operation with previous setting.

ƒWhen fan speed is changed, quiet operation is shifted to quiet operation of the new fan speed.

ƒWhen operation mode is changed, quiet operation is shifted to quiet operation of the new mode.

ƒDuring quiet operation, if ON timer activates, quiet operation maintains.

ƒAfter off, when on back, quiet operation is not memorised.

šControl contents

oAuto fan speed is change from normal setting to quiet setting of respective fan speed. This is to reduce sound of Hi, Me, Lo for 3dB.

oManual fan speed for quiet operation is -1 step from setting fan speed.

12.6Quiet Operation (Heating)

šPurpose

o To provide quiet heating operation compare to normal operation.

šControl condition

o Quiet operation start condition

ƒWhen “Quiet” button at remote control is pressed.

Quiet LED illuminates.

oQuiet operation stop condition

ƒWhen one of the following conditions is satisfied, quiet operation stops:

šPowerful button is pressed.

šStop by OFF/ON button.

šTimer “off” activates.

šQuiet button is pressed again.

ƒWhen quiet operation is stopped, operation is shifted to normal operation with previous setting.

ƒWhen fan speed is changed, quiet operation is shifted to quiet operation of the new fan speed.

ƒWhen operation mode is changed, quiet operation is shifted to quiet operation of the new mode.

ƒDuring quiet operation, if timer “on” activates, quiet operation maintains.

ƒAfter off, when on back, quiet operation is not memorised.