16.4.21F91 (Refrigeration Cycle Abnormality)

16.4.21F91 (Refrigeration Cycle Abnormality)

Malfunction Decision Conditions

šDuring cooling, compressor frequency = Fcmax.

šDuring cooling and heating operation, running current: 0.65A < I < 1.65A.

šDuring cooling, indoor intake - indoor pipe < 39.2°F.

Malfunction Caused

šRefrigerant shortage (refrigerant leakage)

šPoor compression performance of compressor.

š2/3 way valve closed.

šDetection error due to faulty indoor intake air or indoor pipe temperature sensors.

Troubleshooting