16.4.2H12 (Indoor/Outdoor Capacity Rank Mismatched)

16.4.2H12 (Indoor/Outdoor Capacity Rank Mismatched)

Malfunction Decision Conditions

šDuring startup, error code appears when different types of indoor and outdoor units are interconnected.

Malfunction Caused

šWrong models interconnected.

šWrong indoor unit or outdoor unit PCBs mounted.

šIndoor unit or outdoor unit PCBs defective.

šIndoor-outdoor unit signal transmission error due to wrong wiring.

šIndoor-outdoor unit signal transmission error due to breaking of wire 3 in the connection wires between the indoor and outdoor units.