Panasonic Indoor Unit Outdoor Unit CS-E9NKUAW CS-E12NKUAW CU-E9NKUA CU-E12NKUA Malfunction Caused

Models: Indoor Unit Outdoor Unit CS-E9NKUAW CS-E12NKUAW CU-E9NKUA CU-E12NKUA

1 90
Download 90 pages 44.12 Kb
Page 48
Image 48
16.4 Self-diagnosis Method

16.4 Self-diagnosis Method

16.4.1H11 (Indoor/Outdoor Abnormal Communication)

Malfunction Decision Conditions

šDuring startup and operation of cooling and heating, the data received from outdoor unit in indoor unit signal transmission is checked whether it is normal.

Malfunction Caused

šFaulty indoor unit PCB.

šFaulty outdoor unit PCB.

šIndoor unit-outdoor unit signal transmission error due to wrong wiring.

šIndoor unit-outdoor unit signal transmission error due to breaking of wire in the connection wires between the indoor and outdoor units.

šIndoor unit-outdoor unit signal transmission error due to disturbed power supply waveform.

Troubleshooting

48

Page 48
Image 48
Panasonic Indoor Unit Outdoor Unit CS-E9NKUAW CS-E12NKUAW CU-E9NKUA CU-E12NKUA Self-diagnosisMethod, Malfunction Caused