5Chimney Requirements

R

3100 Wood Stove Series (ACC)

 

5Chimney Requirements

 

A. Venting Components

B. Chimney Systems

Chimney Connector:

It is also known as flue pipe or stove pipe. The chimney connector joins the stove to the chimney. It must be a 6 inch (152mm) minimum diameter 24 gauge mild steel black or 26 gauge blued steel, or an approved air-insulated double wall venting pipe.

Thimble:

A manufactured or site-constructed device installed in combustible walls through which the chimney connector passes to the chimney. It is intended to keep the walls from igniting. Site constructed thimbles must meet NFPA 211 Standards. Prefabricated must be suitable for use with selected chimney and meet UL103 Type HT Standards. Follow instructions provided by the manufacturer for manufactured thimbles for masonry chimney and prefabricated chimneys.

Chimney:

The chimney can be new or existing, masonry or prefabricated and must meet the following minimum requirements specified in Section 5B.

Listed Termination Cap

Roof Brace (if required)

Storm Collar

Flashing

Prefabricated Metal Chimney

Must be a 6 inch (152mm) diameter (ID) high temperature chimney listed to UL 103 HT (2100oF) or ULC S629M.

Must use components required by the manufacturer for installation.

Must maintain clearances required by the manufacturer for installation.

Refer to manufacturers instructions for installation.

NOTE: In Canada when using a factory-built chimney it must be safety listed, Type UL103 HT (2100oF) CLASS “A” or conforming to CAN/ULC-S629M, STANDARD FOR 650oC

FACTORY-BUILT CHIMNEYS.

Listed Termination Cap

Storm Collar

Flashing

Listed Chimney

Ceiling Support

Trim Collar on

Inside Wall

Chimney

Connector

Floor

Protector

Listed Chimney

Insulated " T "

Wall Support

Chimney Connector

Floor Protector

Figure 16.1 Prefabricated Exterior Chimney

Figure 16.2 - Prefabricated Interior Chimney

 

 