Quadra-Fire 31M-ACC-MBK Wood Stove Series ACC, D. Chimney Termination Requirements, E.2-10-3Rule

Models: 31ST-ACC 31M-ACC-MBK 31M-ACC-NT 31M-ACC-GT

1 48
Download 48 pages 14.43 Kb
Page 19
Image 19
D. Chimney Termination Requirements

R

3100 Wood Stove Series (ACC)

D. Chimney Termination Requirements

Follow manufacturers instructions for clearance, securing, flashing and terminating the chimney.

Must have an approved and listed cap

Must not be located where it will become plugged by snow or other material

Must terminate at least 3 feet (91cm) above the roof and at least 2 feet (61cm) above any portion of the roof within 10 feet (305cm).

NOTE:

Chimney performance may vary.

Trees, buildings, roof lines and wind conditions affect performance.

Chimney height may need adjustment if smoking or overdraft occurs.

Must be located away from trees or other struc- tures

E.2-10-3 Rule

These are safety requirements and are not meant to assure proper flue draft.

 

Less than 10 ft. (305cm)

 

 

2 ft. (61cm)

3 ft. (91cm)

 

2 ft. (61cm)

Minimum

 

10 ft. (305cm) To Nearest Roofline

 

 

3 ft. (91cm)

 

 

Minimum

 

 

Figure 19.1

Pitched Roof

 

 

Less than 10 ft. (305cm)

 

 

2 ft. (61cm)

3 ft. (91cm)

 

2 ft. (61cm)

Minimum

 

10 ft. (305cm) To Nearest Roofline

 

 

3 ft. (91cm)

 

 

Minimum

 

 

Figure 19.2

Pitched Roof

 

March 2, 2007

7033-277C

Page 19

Page 19
Image 19
Quadra-Fire 31M-ACC-MBK, 31ST-ACC, 31M-ACC-GT Wood Stove Series ACC, D. Chimney Termination Requirements, E.2-10-3Rule