C. Equivalent Feet of Pipe

Castile Pellet Stove

R

C. Equivalent Feet of Pipe

The table below can help you calculate the equivalent feet of pipe which is a method used to determine pellet vent size.

See Figure 11.1

See Figure 11.1 WARNING

Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to the owner’s information manual provided with this appli- ance. For assistance or additional information consult a qualified installer, service agency or your dealer.

Example of 3 Elbow-Rear Vent Termination Calculaton

D. Pipe Selection Chart 2 ft.

ALTITUDE IN THOUSANDS OF FEETManual backgroundManual backgroundManual backgroundManual background 3 ft.

Pellet Venting

# of

Feet of

Multipled

Equivalent

Components

Component

Elbows

Pipe

By

Feet

Equivalent Feet

90o Elbow or Tee

3

 

X

5

15

45o Elbow

 

 

X

3

 

Horizontal Pipe

 

7

X

1

7

Vertical Pipe

 

2

X

0.5

1

2 ft.

Total Equivalent Feet

23

2 ft.

 

Note: This is a generic example and is not

 

 

 

intended to represent any specific fuel type.

Figure 11.1

D. Pipe Selection Chart

The chart will help you in determing proper vent- ing size according to the equivalent feet of pipe calcuated above and the altitude above sea level of this installation. See Figure 11.2.

Locate the calculated equivalent feet of pipe on the vertical left side of the chart. Move to the right horizontally on the chart until you reach your altitude above sea level.

If you fall below the diagonal line, 3 or 4 inch (76 to 102mm) pipe may be used. If it is anywhere above the diagonal line, a 4 inch (102mm) diam- eter pipe is recommended.

The chart reveals that a 90° elbow is 5 times as restrictive to the flow of exhaust gases under positive pressure as 1 foot of horizontal pipe, and a foot of horizontal pipe is twice as restrictive as a foot of vertical pipe.

30

4 in. (102mm) Diameter Pipe Recommended

 

20

 

 

 

 

 

 

 

 

 

Equivalent Pipe

 

 

 

 

 

 

 

 

 

Length In Feet

 

 

 

 

 

 

 

 

 

0

3 in. or 4 in. (76mm or 102mm) Diameter Pipe

2

3

4

5

6

7

8

9

10

1

ALTITUDE IN THOUSANDS OF FEET

Figure 11.2

October 11,, 2005

250-6422D

Page 11

Page 11
Image 11
Quadra-Fire CASTILE-PMH, CASTILE-MBK C. Equivalent Feet of Pipe, D. Pipe Selection Chart, Castile Pellet Stove, See Figure

FAQ

What is the equivalent feet of pipe calculation method?

The equivalent feet of pipe calculation method is a way to determine the proper pellet vent size.

What components are included in the equivalent feet of pipe calculation?

The equivalent feet of pipe calculation includes components such as elbows, pipe, and their respective multiplications.

What is the purpose of the Pipe Selection Chart?

The Pipe Selection Chart helps in determining the proper venting size according to the equivalent feet of pipe calculated and the altitude above sea level of the installation.