D. Vent Diagrams
WARNING
Fire Risk. Explosion Risk.
Do NOT pack insulation or other combustibles between ceiling firestops.
•ALWAYS maintain specified clearances around venting and firestop systems.
•Install wall shield and ceiling firestops as specified.
Failure to keep insulation or other material away from vent pipe may cause fire.
1.Top Vent - Horizontal Termination One Elbow
V1
H1
Figure 5.3
Two Elbows
Note: Must have a 12 inches minimum vertical vent before attaching a 90° elbow to the unit.
H2 | H1 |
|
V1 Minimum | H1 Maximum | ||
1 ft. | 305 mm | 3 ft | 924 mm |
762 mm | 6 ft | 1.8 m | |
1.7 m | 9 ft | 2.7 m | |
4 ft. | 1.2 m | 10 ft | 3.1 m |
1.4 m | 12 ft | 3.7 m | |
1.7 m | 15 ft | 4.6 m | |
2 m | 18 ft | 5.5 m | |
2.3 m | 21 ft | 6.4 m |
H1 = 21 ft. (6.4 m) Maximum
V1 = 40 ft. (12.2 m) Maximum
V1 + H1 = 30 ft. (9.1 m) Maximum*
Note: Must have a 12 inch minimum vertical vent before attaching a 90° elbow to the unit.
*If the horizontal component is less than 5 feet then the total vent run can be extended to 40 feet.
|
| V1 Minimum | H1 + H2 Maximum | |||
|
| 1 ft. | 305 mm | 3 ft | 924 mm | |
|
| 762 mm | 6 ft | 1.8 m | ||
|
| 1.7 m | 9 ft | 2.7 m | ||
|
| 4 ft. | 1.2 m | 10 ft | 3.1 m | |
|
| 1.4 m | 12 ft | 3.7 m | ||
|
| 1.7 m | 15 ft | 4.6 m | ||
|
| 2 m | 18 ft | 5.5 m | ||
|
| 2.3 m | 21 ft | 6.4 m | ||
|
| V1 = 40 ft. (12.2 m) Maximum | ||||
|
| H1 + H2 = 21 ft. (6.4 m) Maximum | ||||
| ||||||
|
| V1 + H1 + H2= 30 ft. (9.1 m) Maximum* | ||||
V1 | ||||||
|
|
|
|
* If the horizontal component is less than 5 feet then the total vent run can be extended to 40 feet.
INSTALLED
HORIZONTALLY
Figure 5.4
14 |