Quadra-Fire QV36A-FB Top Vent - Vertical Termination - continued, Three Elbows, V2 VT HT H1

Models: QV36A-FB

1 59
Download 59 pages 13.27 Kb
Page 17
Image 17
2. Top Vent - Vertical Termination - (continued)

2. Top Vent - Vertical Termination - (continued)

Three Elbows

VT Min.

HT Max.

1 ft. 6 in.

3 ft.

 

Note: A section of vertical pipe (12 inches minimum)

2 ft. 6 in.

6 ft.

 

 

MUST be installed prior to attaching a 90° elbow.

3 ft. 6 in.

9 ft.

 

4 ft.

10 ft.

 

4 ft. 6 in.

12 ft.

 

5 ft. 6 in.

15 ft.

 

6 ft. 6 in.

18 ft.

 

7 ft. 6 in.

21 ft.

 

HT = 21 ft. Max

 

 

VT = 40 ft. Max

 

 

VT + HT = 30 ft. Max*

 

* If the horizontal component is less than

 

5 feet then the total vent run can be

 

extended to 40 feet.

 

V2

VT

HT

H1

H2

V1

INSTALLED

HORIZONTALLY

Figure 5.8

Quadra-Fire • Expression 36 (QV36A-FB)2062-900 Rev. S • 11/11

17

Page 17
Image 17