Quadra-Fire QV36A-FB Top Vent - Vertical Termination No Elbow, V1 = 40 ft. Max. 12.2 m, VT Min

Models: QV36A-FB

1 59
Download 59 pages 13.27 Kb
Page 16
Image 16
2. Top Vent - Vertical Termination

2. Top Vent - Vertical Termination

No Elbow

V1 = 40 ft. Max. (12.2 m)

V1

Figure 5.6

Two Elbows

Note: A section of vertical pipe (12 inches minimum)

MUST be installed prior to attaching a 90° elbow.

VT Min.

HT Max.

1

ft. 6

in.

3

ft.

2

ft. 6

in.

6

ft.

3

ft. 6

in.

9

ft.

 

 

 

 

 

4 ft.

 

10 ft.

 

 

4 ft. 6 in.

12 ft.

5 ft. 6 in.

15 ft.

6 ft. 6 in.

18 ft.

 

 

7 ft. 6 in.

21 ft.

 

 

 

 

 

HT = 21 ft. Max

VT = 40 ft. Max

VT + HT = 30 ft. Max*

VT

HT

*If the horizontal component is less than 5 feet then the total vent run can be extended to 40 feet.

Figure 5.7

16

Quadra-Fire • Expression 36 (QV36A-FB)2062-900 Rev. S • 11/11

Page 16