Quadra-Fire QV36A-FB owner manual Vent Clearances and Framing, A. Pipe Clearances to Combustibles

Models: QV36A-FB

1 59
Download 59 pages 13.27 Kb
Page 18
Image 18
6 Vent Clearances and Framing

6 Vent Clearances and Framing

A. Pipe Clearances to Combustibles

A. Pipe Clearances to Combustibles WARNING

Fire Risk. Explosion Risk.

Maintain vent clearance to combustibles as specified.

Do not pack air space with insulation or other materials.

Failure to keep insulation or other materials away from vent pipe may cause fire.

3 in. TOP CLEARANCE

1 in. CLEARANCE AROUND VERTICAL SECTIONS

1 in. SIDE AND BOTTOM CLEARANCE

Figure 6.1 Pipe Clearances

B. Wall Penetration Framing

Combustible Wall Penetration

Frame a hole in a combustible wall for an interior wall shield firestop, (Figure 6.2) whenever a wall is penetrated. Use same size framing materials as those used in the wall construction. The wall shield firestop maintains minimum clearances and prevents cold air infiltration.

Non-Combustible Wall Penetration

If the hole being penetrated is surrounded by noncombus- tible materials such as concrete, a hole with diameter one inch greater than the pipe is acceptable.

Whenever a non-combustible wall is penetrated, the wall shield firestop is only required on one side and no heat shield is necessary.

If your local inspector requires the wall shield firestop on both sides, then both wall shield firestops must have a heat shield attached to them.

Note: The top standoff is flat on top of the unit for shipping purposes. The two pieces should be folded up as shown and connected together by interlocking tabs and slots on each piece.

VENT FRAMING HOLE* (Do NOT pack with B. Wall Penetration Framing Insulation)

53-3/4 in.

1365 mm

54-3/4 in.

1391 mm

*Shows center of vent framing hole for top venting. The center of the hole is one (1) inch (25.4 mm) above the center of the horizontal vent pipe.

Figure 6.2 Exterior Wall Hole

18

Quadra-Fire • Expression 36 (QV36A-FB)2062-900 Rev. S • 11/11

Page 18
Image 18
Quadra-Fire QV36A-FB Vent Clearances and Framing, A. Pipe Clearances to Combustibles, B. Wall Penetration Framing