Raypak 503-2003 manual Gas Supply Connection, Gas Supply Pressure

Models: 503-2003

1 56
Download 56 pages 27.2 Kb
Page 19
Image 19
Automatic Chlorinators and

Further advice should be obtained from your pool or spa builder, accredited pool shop, or chemical suppli- er for the correct levels for your water.

Automatic Chlorinators and

Chemical Feeders

All chemicals must be introduced and completely dilut- ed into the pool or spa water before being circulated through the heater. Do not place sanitizing chemicals in the skimmer. High chemical concentrations will result when the pump is not running (e.g. overnight).

Chlorinators must feed downstream of the heater and have an anti-siphoning device to prevent chemical back-up into the heater when the pump is shut off.

NOTE: High chemical concentrates from feeders and chlorinators that are out of adjustment will cause rapid corrosion to the heat exchanger. Such damage is not covered under the warranty.

NOTE: Failure of a heat exchanger due to lime scale build-up on the heating surface, low pH or other chemical imbalance is non-warrantable.

Gas Supply

DANGER: Make sure the gas on which the heater will operate is the same type as specified on the heater’s rating plate.

Gas piping must have a sediment trap ahead of the heater gas controls, and a manual shut-off valve lo- cated outside the heater jacket. It is recommended that a union be installed in the gas supply piping adja- cent to the heater for servicing. The gas supply pressure to the heater must not exceed 10.5 in. WC for natural gas or 13.0 in. WC for propane gas. A pounds- to-inches regulator must be installed to reduce the gas supply pressure if it is higher than noted above. This regulator should be placed a minimum distance of 10 times the pipe diameter upstream of the heater gas controls. Refer to Table I for maximum pipe lengths.

Gas Supply Connection

CAUTION: The heater must be disconnected from the gas supply during any pressure testing of the gas supply system at test pressures in excess of 1/2 psi (3.45 kPa).

The heater must be isolated from the gas supply pip- ing system by closing the upstream manual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psi (3.45 kPa). Relieve test pressure in the gas supply line prior to re-connecting the heater and its manual shut-off valve to the gas supply line. FAILURE

TO FOLLOW THIS PROCEDURE MAY DAMAGE THE GAS VALVE. Over-pressurized gas valves are not covered by warranty. The heater and its gas con- nections shall be leak-tested before placing the appliance in operation. Use soapy water for leak test. DO NOT use an open flame.

Fig. 17: GasGas SupplySupply Connection

CAUTION: Do not use Teflon tape on gas line pipe thread. A pipe compound rated for use with natural and propane gases is recommended. Apply sparingly only on male pipe ends, leaving the two end threads bare.

CAUTION: Support gas supply piping with hangers, not by the heater or its accessories. Make sure the gas piping is protected from physical damage and freezing, where required.

Gas Supply Pressure

A minimum of 4.0 in. WC and a maximum of 10.5 in. WC upstream gas pressure is required under load and no-load conditions for natural gas. A minimum of 4.0 in. WC and a maximum of 13.0 in. WC is required for propane gas. The gas pressure regulator(s) supplied on the heater is for low-pressure service. If upstream pressure exceeds these values, an intermediate gas pressure regulator, of the lockup type, must be installed.

When connecting additional gas utilization equipment to the gas piping system, the existing piping must be checked to determine if it has adequate capacity for the combined load.

19

Page 19
Image 19
Raypak 503-2003 manual Gas Supply Connection, Gas Supply Pressure, Automatic Chlorinators and Chemical Feeders