2.FOR REFERENCE ONLY: Measure the blower amp draw with the heater firing at 100% input and compare the measured value to the values in Table U. The amp draw is measured with a clamp- on type amp probe clamped to the 14 AWG black power wire going into the blower.
3.When firing at 100%, the desired heater combus- tion CO2 is between 8.5 and 9.0% for natural gas and 9.5 and 10.0% for propane with CO less than 100 ppm. If this combustion cannot be achieved with the blower suction within the tolerances spec- ified in Table T, contact the factory. The reference amp draw reading may help to indicate if there is a problem with the system or if blower adjustment is required.
Manifold Check
1.Check manifold gas pressure at the gas valve out- let pressure tap (connection “D” in Fig. 47). This pressure should read per the values in Table V for natural and propane gas.
2.If the pressure reading differs by more than ± 0.2 in. WC, STOP – Call the factory for directions on what to do next!
| Model |
| Air Pressure |
| Setting |
|
|
|
|
| |||
|
| Setting (in. WC) |
| Tolerance |
| |
| 503 |
|
| ± 0.2 in. WC |
| |
| 753 |
|
| ± 0.2 in. WC |
| |
| 1003 |
|
| ± 0.2 in. WC |
| |
| 1253 |
|
| ± 0.2 in. WC |
| |
| 1503 |
|
| ± 0.2 in. WC |
| |
| 1753 |
|
| ± 0.2 in. WC |
| |
| 2003 |
|
| ± 0.2 in. WC |
| |
| Table T: |
| MVB Air Pressure |
| Settings |
Model | Amp Draw | Setting |
Tolerance | ||
503 | 1.9 | |
753 | 2.9 | |
1003 | 4.8 | |
1253 | 6.3 | |
1503 | 8.1 | |
1753 | 10.5 | |
2003 | 13.0 |
Table U: MVB Amp
Model | Manifold Gas Pressure Setting | |
High Fire Values (in. WC) | ||
| Natural Gas | Propane Gas |
503 | ||
753 | ||
1003 | ||
1253 | ||
1503 | ||
1753 | ||
2003 |
Table V: MVB Manifold Pressure Settings
CAUTION: Special manifold and air settings may be required.
Finishing
1.Record all data on the
2.Disconnect the manometers and reconnect the cap on the fan pressure switch tee and reinsert the sealing screws into the bleedle valves.
3.
Safety Inspection
1.Check all thermostats and high limit settings.
2.During the following safety checks leave manome- ters hooked up, check and record.
3.If other
4.Check thermostats for
5.Check high limits for
6.While in operation, check flow switch operation.
7.Check the low gas pressure switch (if provided). (For proper adjustment, use the attached manometers, if available, to set pressure. The scales on the switch are approximate only.) Low
43