Rank | Item Field | Number Field | Type | Fault Description |
0 | E01 | Err | Error | EEPROM error |
1 | FP | Err | Warning | Flame proof warning |
2 | BOIL OUT | SHr | Error | Boiler outlet sensor short |
3 | BOIL OUT | OPn | Error | Boiler outlet sensor open |
4 | BOIL IN | SHr | Error | Boiler inlet sensor short |
5 | BOIL IN | OPn | Error | Boiler inlet sensor open |
6 | SUP | SHr | Error | System sensor short |
7 | SUP | OPn | Error | System sensor open |
8 | OUTDR | SHr | Error | Outdoor sensor short |
9 | OUTDR | OPn | Error | Outdoor sensor open |
10 | DHW | SHr | Error | DHW sensor short |
11 | DHW | OPn | Error | DHW sensor open |
|
| Table R: Error Codes |
|
|
WWSD - Selects the outdoor temperature that shuts | Item Field |
|
| Menu Field | |
the heater off, no matter what the demand. NOTE: The | Displays an |
|
| Displays the current menu | |
WWSD segment will be displayed on the LCD. | name of the |
|
|
|
|
| abbreviated |
|
|
| Number Field |
Operation | selected item |
|
|
| |
|
|
| Displays the | ||
|
|
|
| current value of | |
|
|
|
|
| the selected |
The Raypak modulating temperature control uses a |
|
|
|
| item |
|
| DHW | External Input | Status Field | |
Liquid Crystal Display (LCD) as a method of supply- |
|
| Modulation | Offset Signal | Displays the |
ing information. The LCD is used to setup and monitor |
| { |
| Modulating | current status |
system operation by means of three push buttons |
|
| inputs, outputs | ||
(Item, ▲ and ▼) shown at the bottom of Fig. 36. |
|
|
| of the control’s | |
Buttons |
| Control | and operation | ||
All items displayed by the control are organized into | Item |
|
| ||
Menus, |
|
| |||
two menus, the view menu and the adjust menu. The | Selects |
|
| ||
adjusts |
|
|
| ||
active menu is displayed in the upper right hand side | Items and |
|
|
| |
settings |
|
|
| ||
of the display in the menu field. The default menu is | Fig. 36: Modulating Temperature Control Display | ||||
the view menu. | |||||
When the temperature control is powered up, the con- | To make an adjustment to a setting in the control, | ||||
trol turns on all segments in the display for 2 seconds, | begin by selecting the “ADJUST” menu. To change | ||||
then the software version is displayed for 2 seconds. | from the view menu to the adjust menu, simultaneous- | ||||
At the end of that 4 second period, the control enters | ly press and hold all three buttons for 1 second. The | ||||
the normal operating mode and “VIEW” is displayed. | menu name, “ADJUST” will be displayed in the menu | ||||
Pressing the scroll button “scrolls” through the dis- | field. |
|
|
|
|
played values in the “VIEW” menu. | The menu will automatically revert back to the view | ||||
| menu after 20 seconds of keyboard inactivity. Then | ||||
| scroll to the desired item using the scroll button. Fi- | ||||
| nally, use the ▲ or ▼ button to make the adjustment. | ||||
| In the absence of other information, the values pro- | ||||
| vided in Table Q should be used as default settings. |
35