Definitions
NOTE: The defined terms are not active in all modes of control operation.
%OUT - Current percent modulation rate of heater.
BOIL DSGN - Design boiler water temperature used in heat loss calculations.
BOIL MASS - This setting allows adjustment in the field for high or low thermal masses; High thermal mass (setting=3) provides slower reaction, lower ther- mal mass (setting=1) provides faster reaction.
BOIL MAX - Highest outlet water temperature that the control is allowed to use as a target temperature. BOIL MIN - Lowest outlet water temperature that the control is allowed to use as a target temperature. BOIL ON - Accumulated runtime of heater (up to 999 hours, then resets to 0).
BOIL OUT - Actual heater outlet water temperature. BOIL START - Starting boiler water temperature. BOIL SUP - Actual system supply water temperature. BOIL TARGET - Target temperature that the heater is trying to maintain.
‘BURNER’ DELAY - Holds control output at ignition setting from the start of the ignition sequence to the specified burner delay time (0 to 3:00 min.).
DEM 1 - Indicates 24 VDC signal has been supplied to the H+D terminal.
DEM 2 - Indicates 24 VDC Flame Proof signal is pres- ent.
DIFF - The operating differential of the heater; The heater outlet water temperature is allowed to rise above the BOIL TARGET temperature by 1⁄2 of this dif- ferential before the heater shuts off. For example, if the heater target temperature is set to 160°F (71°C) and the differential is set to 10°F (5°C), on temperature rise, the heater will shut off at 165°F (74°C). Once the heater shuts off, it will not come on again until the tem- perature falls to 155°F (68°C).
EXTERNAL INPUT SIGNAL – Selects external input signal range
34
FP - Flame proof warning.
MODE - Operating mode of the heater.
OFFSET - The Offset setting allows the boiler target temperature to be fine tuned to the external input sig- nal. The control reads the external input signal and converts this to a boiler target temperature. The Offset setting is then added to the boiler target temperature. OUTDR - Outdoor air temperature.
OUTDR DESIGN - Design outdoor air temperature used in the heat loss calculation.
OUTDR START - Starting outdoor air temperature. PUMP DLY - Sets the operating time of the pump once the CFH is satisfied.
TANK - Current DHW tank temperature (Mode 3). TANK DIFF - Storage tank differential (Mode 3). TANK TARGET - Target temperature in the DHW storage tank (Mode 3).
UNITS - Selects the temperature units to be displayed (°F or °C).