WARNING: Using a
Check the power source:
AC = 108 VAC Minimum, 132 VAC MAX AB = 108 VAC Minimum, 132 VAC MAX BC = <1 VAC Maximum
FRONT WIRING PANEL LOW VOLTAGE ELECTRICAL CONNECTIONS
Fig. 18: Wiring Electrical Connections
Field-Connected Controllers
It is strongly recommended that all
NOTE:
NOTE: Minimum 18 AWG, 105°C, stranded wire must be used for all low voltage (less than 30 volts) external connections to the unit. Solid conductors should not be used because they can cause excessive tension on contact points. Install conduit as appropriate. All high voltage wires must be the same size (105°C, stranded wire) as the ones on the unit or larger.
Check the Power Source
BLACK CIRCUIT
BREAKER
WHITE
GREEN
GROUND
A B C
Fig. 19: Wiring Connections
Fig. 20:
Making the Electrical Connections
Refer to Fig.
1.Verify that circuit breaker is properly sized by referring to heater rating plate. A dedicated circuit breaker should be provided.
2.NOTE: Current draw noted on rating plate does not include pump current.
3.Turn off all power to the heater. Verify that power has been turned off by testing with a
4.Observe proper wire colors while making electri- cal connections. Many electronic controls are polarity sensitive. Components damaged by im- proper electrical installation are not covered by warranty.
5.Provide overload protection and a disconnect means for equipment serviceability as required by local and state code.
6.Install heater controls, thermostats, or building management systems in accordance with the applicable manufacturers’ instructions.
7.Conduit should not be used as the earth ground.
21