| Boiler Target |
0 | 0 | |
1 | 2 | 50°F |
2 | 4 | 68.9°F |
3 | 6 | 87.8°F |
4 | 8 | 106.7°F |
5 | 10 | 125.6°F |
6 | 12 | 144.1°F |
7 | 14 | 163.3°F |
8 | 16 | 182.2°F |
9 | 18 | 201.1°F |
10 | 20 | 220°F |
*Requires a 500Ω resistor.
Table O:
|
| Boiler Target |
0 | 0 | |
1 | 2 | |
2 | 4 | 50°F |
3 | 6 | 71.3°F |
4 | 8 | 92.5°F |
5 | 10 | 113.8°F |
6 | 12 | 135°F |
7 | 14 | 156.3°F |
8 | 16 | 177.5°F |
9 | 18 | 198.8°F |
10 | 20 | 220°F |
*Requires a 500Ω resistor.
Table P:
Item | Modes | Default Setting | Range | |
| 1, | 2 | 160°F | OFF, 70 to 220°F |
Boil Target | 3 |
| 160°F | OFF, 70 to 190°F |
| 4, 5, 6, 7 | 180°F | OFF, 70 to 220°F | |
Boil Max | 1, 2, 4, 5, 6, 7, 8 | 200°F | OFF, 120 to 225°F | |
3 |
| 180°F | OFF, 120 to 190°F | |
Boil Min | 1, 2, 3, 4, 5, 6, 7 | 150°F | OFF, 80 to 180°F | |
‘Burner’ Delay | All | 0:00 min | 0:00 to 3:00 min | |
Boil Mass | All | 1 (Low) | 1 (Low), 2 (Med), 3 (High) | |
Diff | 1, 2, 3, 4, 5, 6, 7 | Auto | Auto, 2 to 42°F | |
DHW Target | 3 |
| 120°F | OFF, 70 to 190°F |
DHW Diff | 3 |
| 5°F | 2 to 10°F |
‘Pump’ Dly | All | 3:00 min | OFF, 0:20 to 9:55 min, ON | |
Outdr Start | 4, 5 | 70°F | 35 to 85°F | |
Outdr Design | 4, 5 | |||
Boil Start | 4, 5 | 135°F | 35 to 150°F | |
Boil Dsgn | 4, 5 | 180°F | 120 to 220°F | |
WWSD | 4, 5 | 70°F | 35 to 100°F | |
Units | All | °F | °F or °C | |
Mode | N/A | 2 | 1, 2, 3, 4, 5, 6, 7, 8 | |
External Input Signal | 6, 7 | 2 to 10 VDC | 2 to 10 VDC or 0 to 10 VDC | |
Offset | 6, 7 | 0°F |
Table Q: Temperature Control Default Setpoints
33