Image 50
As Required

6.Perform leakage test on gas valves. (See Fig. 48.)

7.Test air switch in accordance with manufacturer’s instructions. (Turn panel switch to the “On” posi- tion until blower is proven, then turn the switch to “Off.”

8.Inspect and clean burner using shop air.

As Required

1.Recondition or replace low water cut-off device (if equipped).

2.Check drip leg and gas strainers.

3.Check flame failure detection system. (See “Post Start-Up Check,” page 45.)

4.Check igniter. (Resistance reading should be 42- 70 ohms at ambient temperature).

5.Check flame signal strength. (Flame signal should be greater than 1 microampere as measured at the 2 pins on the upper left corner of the ignition control).

6.Check firing rate control by checking the manifold pressure. (See “Manifold Check” on page 43.)

7.Test safety/safety relief valves in accordance with ASME Heater and Pressure Vessel Code Section IV.

Filter Maintenance

NOTE: Use Raypak replacement filters, kit number 012552F (12”X12”) for models 503-1003 and kit number 012553F (16”X16”) for models 1253-2003.

Inspect quarterly

Replace when tracking pressure exceeds -0.5 in. WC at 100% fan speed, except for models 1003, 1753 and 2003, which need to be replaced when tracking pressure exceeds -0.7 in. WC at 100% fan speed.

Filter Replacement

1.Remove the filter box cover by loosening and removing the two wing nuts holding it in place.

Fig. 49: Remove the Air Filter Box Cover

2.Remove the filter by lifting it straight up and out of the slot in the filter box.

Fig. 50: Remove the Air Filter

3.Reverse steps 1 and 2 to install the new filter. Use Raypak replacement filters, kit number 012552F (12”X12”) for models 503-1103 and kit number 012553F (16”X16”) for models 1253-2003.

50