Monitoring and Operating the Controller
4.11.6Error Codes
Table 4-16 Procedure for Accessing Accutune Error Codes
Step
Operation
Press
Result
1Select Accutune
2Go to Error Code
Prompt
Setup
Function
Upper Display = SET
Lower Display = ATUNE
Upper Display = (an error code)
Lower Display = ATERR
Table
Table 4-17 Accutune Error Codes
Error Code |
|
|
(Upper Display) | Definition | Fix |
RUN | ACCUTUNE RUNNING | The Accutune process is still active (Read Only) |
NONE | NO ERRORS OCCURRED | None |
| DURING LAST ACCUTUNE |
|
| PROCEDURE |
|
IDFL
ABRT
SP2
PROCESS IDENTIFICATION FAILURE
Autotune has aborted because an illegal value of GAIN, RATE, or reset was calculated.
CURRENT ACCUTUNE PROCESS ABORTED caused by the following conditions:
a. Operator changed to Manual mode
b. Digital Input detected c. In Heat region of output and a Cool output calculated or vice versa.
LSP2 not enabled or LSP1 or LSP2 not in use (only applies to Duplex Tuning)
•Illegal Values
– try Accutune again.
•untunable process
Try Accutune again
Enable LSP2 and configure the desired LSP1 and LSP2 setpoints.
Aborting Accutune
To abort Accutune and return to the last previous operation (SP or output level), press
4/07 | UDC2500 Universal Digital Controller Product Manual | 109 |