| Configuration |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Function Prompt |
| Selection or Range of Setting |
|
|
| Parameter |
| ||||
|
| Lower Display |
| Upper Display |
|
|
| Definition |
| ||||
|
| English | Numeric |
|
| English | Numeric |
|
|
|
|
|
|
|
|
| Code |
|
|
| Code |
|
|
|
|
|
|
|
| A1S1EV | 1103 |
|
|
|
|
|
| If Setpoint Programming is enabled and if |
| ||
|
|
|
|
|
|
|
|
|
| the Alarm Type is configured for Event |
| ||
|
|
|
|
|
|
|
|
|
| On/Off: |
| ||
|
|
|
|
|
|
|
|
|
| ALARM 1 SEGMENT EVENT |
| ||
|
|
|
|
|
|
|
|
|
| whether you want the alarm type chosen in |
| ||
|
|
|
|
|
|
|
|
|
| prompt A1S1TYPE to alarm the beginning or |
| ||
|
|
|
|
|
|
|
|
|
| end of a segment in setpoint Ramp/Soak |
| ||
|
|
|
|
|
|
|
|
|
| programming. |
| ||
|
|
|
|
|
| BEGIN | 0 |
|
| BEGINNING OF SEGMENT |
| ||
|
|
|
|
|
| END | 1 |
|
| END OF SEGMENT |
| ||
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
| Alarms configured for events |
|
|
|
|
|
|
|
|
|
|
| ATTENTION |
| ||
|
|
|
|
|
|
|
|
|
| will not operate |
| on Setpoint Program |
|
|
|
|
|
|
|
|
|
|
| segments of zero length. |
| ||
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
| A1S2TY | 1104 |
|
|
|
|
|
| ALARM 1 SETPOINT 2 |
| ||
|
|
|
|
|
|
|
|
|
| you want Setpoint 2 of Alarm 1 to represent. |
| ||
|
|
|
|
|
|
|
|
|
| The selections are the same as A1S1TYPE. |
| ||
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
| A1S2VA | 1105 |
|
| Value in |
|
|
| ALARM 1 SETPOINT 2 |
| ||
|
|
|
|
|
| engineering units |
|
|
| value at which you want the alarm type |
| ||
|
|
|
|
|
|
|
|
|
| chosen in prompt A1S2TYPE to actuate. |
| ||
|
|
|
|
|
|
|
|
|
| The details are the same as A1S1 VAL. |
| ||
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
| A1S2HL | 1106 |
|
| HIGH | 0 |
|
| ALARM 1 SETPOINT 2 |
| ||
|
|
|
|
|
| A1S1HL. |
| ||||||
|
|
|
|
|
| LOW | 1 |
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
| ||
|
| A1S2EV | 1106 |
|
| BEGIN | 0 |
|
| ALARM 1 SEGMENT EVENT |
| ||
|
|
|
| END | 1 |
|
| A1S1EV. |
| ||||
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
| ||
|
| A2S1TY | 1107 |
|
|
|
|
|
| ALARM 2 SETPOINT 1 |
| ||
|
|
|
|
|
|
|
|
|
| you want Setpoint 1 of Alarm 2 to represent. |
| ||
|
|
|
|
|
|
|
|
|
| The selections are the same as A1S1TYPE. |
| ||
|
|
|
|
|
|
|
|
|
|
| Not applicable with Relay |
| |
|
|
|
|
|
|
|
|
|
| ATTENTION |
| ||
|
|
|
|
|
|
|
|
|
| Duplex unless | using Dual Relay PWA. |
| |
|
|
|
|
|
|
|
|
|
|
|
| ||
|
| A2S1VA | 1108 |
|
| Value in |
|
|
| ALARM 2 SETPOINT 1 |
| ||
|
|
|
|
|
| engineering units |
|
|
| value at which you want the alarm type |
| ||
|
|
|
|
|
|
|
|
|
| chosen in prompt A2S1TYPE to actuate. |
| ||
|
|
|
|
|
|
|
|
|
| The details are the same as A1S1 VAL. |
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
4/07 | UDC2500 Universal Digital Controller Product Manual | 79 |