Monitoring and Operating the Controller

Run/Monitor the program

Prior to running the program, make sure all the “SP PROG” function prompts under the Set Up group “SP RAMP” have been configured with the required data.

“HOLD” appears periodically in the upper display indicating that the program is in the HOLD state.

ATTENTION SP Programmer parameter cannot be changed during RUN state (must be in HOLD state).

Run/Monitor functions

Table 4-26lists all the functions required to run and monitor the program.

Table 4-26 Run/Monitor Functions

Function

 

Press

Result

Set the Local

 

 

 

Upper Display = PV value

 

Lower

 

Setpoint

 

Display

 

Lower Display = SP

 

 

or

To set the Local Setpoint value to where you

 

 

 

 

want the program to start out.

Run State

 

 

 

Initiates the setpoint program.

 

Run

 

 

 

 

 

 

 

Hold

 

RUN” appears in the upper display indicating

 

 

 

 

that the program is running.

Hold State

Run

 

 

Hold

External Hold

To Begin

or

Holds the setpoint program.

HOLD” appears in the upper display indicating that the program is in the HOLD state.

The setpoint holds at the current setpoint.

If one of the Digital Inputs is programmed for the HOLD function, then contact closure places the controller in the HOLD state, if the setpoint program is running.

The upper display will periodically show “HOLD” while the switch is closed.

ATTENTION The keyboard takes priority over the external switch for the RUN/HOLD function.

Reopening the HOLD switch runs the program.

To go back to the beginning of the program.