Troubleshooting/Service
Procedure #4
Table
Table 7-8 Troubleshooting Time Proportional Output Failure
Step | What to do | How to do it |
1 | Make sure the controller is configured | Make Output Algorithm Set Up group function |
| for Time Proportional output. | prompt OUTALG = RLY or RLYD. |
|
| Refer to Section 3 - Configuration. |
2 | Check the field wiring. | Make sure the NO or NC contact wiring is correct. |
|
| Refer to Section 2 - Installation for details. |
3 | Check the output. | Put the controller into Manual mode. Vary the |
|
| output above and below the present value. |
|
| Observe OUT1 indicator on the operator interface. |
|
| Contact should change state. 0 % open, 100 % |
|
| closed. Listen for a click from the relay when the |
|
| OUT1 indicator changes state. |
4 | Check relay. | Change relay. |
5 | Change MCU board. | Installation instructions supplied with the new |
|
| board. |
|
|
|
168 | UDC2500 Universal Digital Controller Product Manual | 4/07 |