Output Calibration
6.2 Current Output Calibration
Introduction
Calibrate the controller so that the output provides the proper amount of current over the desired range. The controller can provide an output current range of from 0 to 21 milliamperes and is usually calibrated at 4 mA for 0 % of output and 20 mA for 100 % of output, or any other values between 0 mA and 21 mA. It is not necessary to
Equipment Needed
You will need a standard shop type milliammeter, with whatever accuracy is required, capable of measuring 0 to 20 milliamps.
Calibrator Connections
Refer to Figure
Table 6-1 Set Up Wiring Procedure for Current Output
Step | Action |
|
|
1Apply power and allow the controller to warm up 30 minutes before you calibrate.
2Set LOCK in the Tuning Set Up group to NONE.
3Tag and disconnect the field wiring, at the rear of the controller, from terminals 21
4Connect a milliammeter across these terminals.
Milliammeter
+ _
+ | 19+ | |
_ | 20 | |
21- | ||
|
Figure 6-1 Wiring Connections for Calibrating Current Output
152 | UDC2500 Universal Digital Controller Product Manual | 4/07 |