Configuration

 

Function Prompt

 

Selection or Range of Setting

 

 

Parameter

 

Lower Display

 

Upper Display

 

 

Definition

 

English

Numeric

 

 

English

Numeric

 

 

 

 

 

Code

 

 

 

Code

 

 

 

 

I2 MIN

107

 

 

0.02 to 50.00

 

 

These are the same as above except that

 

 

 

 

 

they apply to Duplex models for the "COOL"

 

or

 

 

 

 

 

 

 

 

 

 

0.02 to 50.00

 

 

zone of Heat/Cool applications or for the

 

I2 RPM

 

 

 

 

 

 

 

 

 

 

 

second set of PID constants.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CYC T1 or

108

 

 

1 to 120

 

 

CYCLE TIME (HEAT) determines the length

 

 

 

 

 

of one time proportional output relay cycle.

 

CT1 X3

 

 

 

 

 

 

 

 

 

 

 

 

 

Defined as "HEAT" cycle time for Heat/Cool

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

applications.

 

 

 

 

 

 

 

 

CYC T1—Electromechanical relays

 

 

 

 

 

 

 

 

CT1 X3—Solid state relays

 

 

 

 

 

 

 

 

 

Cycle times are in either

 

 

 

 

 

 

 

 

ATTENTION

 

 

 

 

 

 

 

 

second or 1/3-

second increments depending

 

 

 

 

 

 

 

 

upon the configuration of RLYTYP in the

 

 

 

 

 

 

 

 

Output Algorithm Set Up group.

 

 

 

 

 

 

 

 

 

 

CYC2T2 or

109

 

 

1 to 120

 

 

CYCLE TIME 2 (COOL) is the same as

 

 

 

 

 

above except it applies to Duplex models as

 

CT2 X3

 

 

 

 

 

 

 

 

 

 

 

 

 

the cycle time in the "COOL" zone of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heat/Cool applications or for the second set

 

 

 

 

 

 

 

 

of PID constants.

 

 

 

 

 

 

 

 

CYC2T2—Electromechanical relays

 

 

 

 

 

 

 

 

CT2 X3—Solid state relays

 

 

 

 

 

 

 

 

 

Cycle times are in either

 

 

 

 

 

 

 

 

ATTENTION

 

 

 

 

 

 

 

 

second or 1/3-

second increments depending

 

 

 

 

 

 

 

 

upon the configuration of RLYTYP in the

 

 

 

 

 

 

 

 

Output Algorithm Set Up group.

 

 

 

 

 

 

 

 

 

 

SECUR

110

 

 

0 to 9999

 

 

SECURITY CODE—The level of keyboard

 

 

 

 

 

lockout may be changed in the Set Up mode.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Knowledge of a security code may be

 

 

 

 

 

 

 

 

required to change from one level to another.

 

 

 

 

 

 

 

 

This configuration should be copied and kept

 

 

 

 

 

 

 

 

in a secure location.

 

 

 

 

 

 

 

 

NOTE: The Security Code is for keyboard

 

 

 

 

 

 

 

 

entry only and is not available via

 

 

 

 

 

 

 

 

communications.

 

 

 

 

 

 

 

 

 

Can only be changed if

 

 

 

 

 

 

 

 

ATTENTION

 

 

 

 

 

 

 

 

LOCK selection

is NONE.

 

 

 

 

 

 

 

 

 

 

LOCK

111

 

 

 

 

 

LOCKOUT applies to one of the functional

 

 

 

 

 

 

groups: Configuration, Calibration, Tuning,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Accutune. DO NOT CONFIGURE UNTIL

 

 

 

 

 

 

 

 

ALL CONFIGURATION IS COMPLETE.

 

 

 

 

 

NONE

0

 

NONE—No lockout; all groups are

 

 

 

 

 

 

 

 

 

 

4/07

UDC2500 Universal Digital Controller Product Manual

37