Honeywell UDC2500 manual Fuzzy Overshoot Suppression, Tune, Accutune, Duplex

Models: UDC2500

1 243
Download 243 pages 28.29 Kb
Page 58
Image 58

Configuration

Function Prompts

Table 3-6 ATUNE Group (Numeric Code 300) Function Prompts

Function Prompt

 

Selection or Range of Setting

 

Parameter

Lower Display

 

Upper Display

 

Definition

English

Numeric

 

English

Numeric

 

 

 

 

Code

 

 

Code

 

 

 

FUZZY

301

 

 

 

 

 

FUZZY OVERSHOOT SUPPRESSION

 

 

 

 

 

 

 

Can be enabled or disabled independently of

 

 

 

 

 

 

 

whether Demand Tuning or SP Tuning is

 

 

 

 

 

 

 

enabled or disabled.

 

 

 

DIS

0

 

 

DISABLE—Disables Fuzzy Overshoot

 

 

 

 

 

Suppression.

 

 

 

 

 

 

 

 

 

 

ENAB

1

 

 

ENABLE—The UDC uses Fuzzy Logic to

 

 

 

 

 

suppress or minimize any overshoot that

 

 

 

 

 

 

 

 

 

 

 

 

 

 

may occur when PV approaches SP. It will

 

 

 

 

 

 

 

not recalculate any new tuning parameters.

 

 

 

 

 

 

 

 

TUNE

302

 

 

 

 

 

ACCUTUNE III

 

 

 

DIS

0

 

 

DISABLE —Disables the Accutune function.

 

 

 

TUNE

1

 

 

DEMAND TUNING—If TUNE is selected,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and tuning is initiated through the operator

 

 

 

 

 

 

 

interface or digital input (if configured), the

 

 

 

 

 

 

 

algorithm calculates new tuning parameters

 

 

 

 

 

 

 

and enters them into the tuning group. This

 

 

 

 

 

 

 

tuning requires no process knowledge and

 

 

 

 

 

 

 

does not require line out for initialization.

 

 

 

 

 

 

 

 

DUPLEX

303

 

 

 

 

 

DUPLEX ACCUTUNING III – These prompts

 

 

 

 

 

 

 

only appear when a duplex output type has

 

 

 

 

 

 

 

been configured.

 

 

 

MANU

 

 

 

MANUAL – Tune manually using LSP 1 and

 

 

 

 

 

 

 

LSP 2 values. LSP 1 is used to derive tuning

 

 

 

 

 

 

 

parameters associated with HEAT (output >

 

 

 

 

 

 

 

50 %). LSP 2 is used to derive tuning

 

 

 

 

 

 

 

parameters associated with COOL (output <

 

 

 

 

 

 

50 %).

 

 

 

AUTO

 

 

 

AUTOMATIC – Tuning is performed

 

 

 

 

 

 

 

automatically on both HEAT and COOL

 

 

 

 

 

 

 

sequentially. LSP 1 is used for HEAT tuning

 

 

 

 

 

 

 

and LSP 2 is used for COOL tuning. To

 

 

 

 

 

 

 

initiate tuning, either LSP 1 or LSP 2 must be

 

 

 

 

 

 

 

in use.

 

 

 

 

 

 

 

 

44

UDC2500 Universal Digital Controller Product Manual

4/07

Page 58
Image 58
Honeywell UDC2500 manual Fuzzy Overshoot Suppression, Tune, Accutune, Duplex