Modbus RTU Function Codes

 

Register Address Structure

 

 

 

 

 

Table 9-1 Integer Parameter Type

 

 

 

 

 

 

 

Register

Name

Access

Notes

 

 

Numbers

 

 

 

 

 

(Dec)

 

 

 

 

 

1

Type = 1

NOT SUPPORTED

16-bit Unsigned Integer

 

 

2

Attribute

NOT SUPPORTED

1 = Read Only,

 

 

 

 

 

2 = Read/Write

 

 

3

Value (16 bit integer)

Read / Write

 

 

 

4

Not Used

NOT SUPPORTED

 

 

 

5

Low Range (16 bit integer)

NOT SUPPORTED

 

 

 

6

Not Used

NOT SUPPORTED

 

 

 

7

High Range (16 bit Integer)

NOT SUPPORTED

 

 

 

8

Not Used

NOT SUPPORTED

 

 

 

9 to 13

Description Text (ASCII string)

NOT SUPPORTED

 

 

 

 

Table 9-2 Floating Point Parameter Type

 

Register

Name

Access

Notes

 

 

Numbers

 

 

 

 

 

(Dec)

 

 

 

 

 

1

Type = 2

NOT SUPPORTED

IEEE Floating Point

 

 

2

Attribute

NOT SUPPORTED

1 = Read Only,

 

 

 

 

 

2 = Read/Write

 

 

3

Value (float high word)

Read / Write

 

 

 

4

Value (float low word)

NOT SUPPORTED

 

 

 

5

Low Range (float high word)

NOT SUPPORTED

 

 

 

6

Low Range (float low word)

NOT SUPPORTED

 

 

 

7

High Range (float high word)

NOT SUPPORTED

 

 

 

8

High Range (float low word)

NOT SUPPORTED

 

 

 

9 to 13

Description Text (ASCII string)

NOT SUPPORTED

 

 

Register Count

The register count depends on the data format of the registers being read or written.

Integer data is represented in sixteen bits and is transferred high byte first. Floating point data is transferred in IEEE 32-bit format.

The register count definitions are:

0001 = Integer Data

0002 = Floating Point Data

4/07

UDC2500 Universal Digital Controller Product Manual

181

Page 195
Image 195